4
Technical specifications
For all modules
General technical specifica
tions of the CPX terminal
Protection class as per EN
60529
Operating voltage supply
Rated voltage
Internal current consumption
at 24 V (internal electronics)
Input modules CPX−2AE−U−I
and CPX−4AE−I
Channels
Input ranges
Cable length
Resolution
Isolation voltage
Potential connection
Conversion time per channel
Module cycle time
Permitted potential difference
between input channels
between inputs and FE
24
Specifications
See CPX system manual
See technical specifications of the
fitted sub−base
V
(electronics/sensors)
EL/SEN
24 V DC ± 25 %
Typ. 50 mA (no current output at
outputs, if available)
Voltage
inputs (only
CPX−2AE−U−I)
2
0 ... 10 V
max. 30 m, screened/shielded
12 bits (A/D converter, internal)
500 V DC
high resistive + capacitive connec
tion to FE
typ. 150 s
2AE−U−I: 4 ms, 4AE−I: 10 ms
AC 1 Vpp
30 V DC
Festo CPX−AX 0503a English
Current
Inputs
2AE..: 2, 4AE−I: 4
0 ... 20 mA/
4 ... 20 mA
0 V AC
30 V DC