7.3 Special parameter settings for DMX/DMH
Some parameters have been adapted to DMX/DMH dosing
pumps. These parameters differ from the default settings
mentioned in the supplier manual for the VFD.
Warning
When resetting the VFD to default settings, the
special parameter settings for DMX/DMH are
overwritten. The special parameters must be set
again.
7.3.1 Mandatory settings
Do not set P506 "automatic fault acknowledgement"
to 6 "always".
Caution
In case of an active error (e. g. short-circuit to earth /
short circuit), the VFD restarts continuously and
damages the system, because P428 is set to 1 "on".
Warning
Danger of malfunction of the VFD with DMX/DMH
dosing pump. Do not change the following settings.
Basic parameters
Code
Parameter
P102
Start-up time
P105
Maximum frequency
Control terminals
Code
Index
Parameter
Setpoint input function
P400
-02
AIN 2 (analog input 2)
Analog ON mode
P401
-01
AIN 1 (analog input 1)
Analog ON mode
P401
-02
AIN 2 (analog input 2)
Adjustment: 0 %
P402
-01
AIN 1 (analog input 1)
Adjustment: 0 %
P402
-02
AIN 2 (analog input 2)
Adjustment: 100 %
P403
-02
AIN 2 (analog input 2)
Digital input function
P420
-01
DIN 1 (digital input 1)
Digital input function
P420
-02
DIN 2 (digital input 2)
Digital input function
P420
-03
DIN 3 (digital input 3)
P428
Automatic starting after mains OFF
* The minimum frequency for the VFD is set to approx. 5 Hz.
Extra functions
Code
Parameter
P504
pulse frequency
P540
mode phase sequence
Modifications of other parameters and adaptation of the inputs
and outputs can be made with the optional "parameter box" or the
"NordCon" software. Observe the supplier manual "BU 0180" for
the VFD provided with the product.
6
Value for DMX/DMH
5 s
100 Hz
Value for DMX/DMH
01 = Setpoint frequency
2 = 0-10 V monitored
2 = 0-10 V monitored
1.36 V*
1 V
5 V
02 = Enable left (left-handed rotation)
19 = Setpoint 1 on/off
20 = Setpoint 2 on/off
1 = On (enable with level)
Value for DMX/DMH
8 kHz
3 = CCW only; only counter-clockwise direction is possible