SCANMASKIN 32 WORLD SERIES
E37
Safe Stop
E038
Overload during low speed
E41
Communication Error
E81
Speed reference error
We strongly recommend that you first find the cause of the fault before clearing it.
Table 53 Error codes
5.6.3 Fault history
When a fault occurs, the inverter stores important performance data at the
moment of the fault. To access the data, use the monitor function (dxxx) and
select d081 details about the present fault. The previous 5 faults are stored in
d082 to d086. Each error shifts d081-d085 to d082-d086, and writes the new error
to d081.
The following Monitor Menu map shows how to access the error codes. When
fault(s) exist, you can review their details by first selecting the proper function:
D081 is the most recent, and D086 is the oldest.
www.scanmaskin.com
Emergency is active
Communication fails between motor drive and PLC
(DSP machines)
The potentiometer on the control panel is dam-
aged
Reset the Emergency stop
Increase the speed
Check the RJ45/Ethernet cable
Inspect the potentiometer
Replace if necessary
ENGLISH