Disassembly And Disposal; Maintenance - SICK WT34 Instrucciones De Operación

Ocultar thumbs Ver también para WT34:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 76
11

Disassembly and disposal

12

Maintenance

8009202.11O1 | SICK
Subject to change without notice
Table 9: Troubleshooting
LED indicator/fault pattern
Yellow LED does not light up
even though the light beam is
aligned to the object and the
object is within the set sensing
range
Object in beam path, no output
signal
Yellow LED flashes; if Alarm is
present then take note of the
corresponding output signal
Yellow LED lights up, no object
in the path of the beam
Object is in the path of the
beam, yellow LED does not
light up
The sensor must be disposed of according to the applicable country-specific regula‐
tions. Efforts should be made during the disposal process to recycle the constituent
materials (particularly precious metals).
NOTE
Disposal of batteries, electric and electronic devices
According to international directives, batteries, accumulators and electrical or
electronic devices must not be disposed of in general waste.
The owner is obliged by law to return this devices at the end of their life to the
respective public collection points.
This symbol on the product, its package or in this document, indicates
that a product is subject to these regulations.
SICK sensors are maintenance-free.
We recommend doing the following regularly:
Clean the external lens surfaces
Check the screw connections and plug-in connections
Cause
No voltage or voltage below
the limit values
Voltage interruptions
Sensor is faulty
Test input (Test) is not con‐
nected properly
Sensor is still ready for opera‐
tion, but the operating condi‐
tions are not ideal
The sensing range distance is
too large
Distance between the sensor
and the object is too long or
sensing range is set too short
Measures
Check the power supply,
check all electrical connec‐
tions (cables and plug connec‐
tions)
Ensure there is a stable power
supply without interruptions
If the power supply is OK,
replace the sensor
Check connection of the test
input. When using female
cable connectors with LED
indicators, make sure the test
input is assigned correspond‐
ingly.
Check operating conditions:
align light beam (light stop)
completely on the object /
cleaning of optical surfaces /
check sensing range and
adjust if necessary.
Reduce the sensing range
Increase the sensing range
13

Publicidad

Tabla de contenido
loading

Tabla de contenido