1. Safety Guidelines
1. Follow the installation instructions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the appli-
cations detailed in these installation instructions. Any other
use will not be considered to comply with requirements
and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out by
authorized persons.
5. Immediately rectify any malfunctions which may influence
safety.
2. Functional description
The MiniPlus fine filter is composed of a body and a rinsable
fine filter insert.
During normal operation, water flows through the filter mesh
to the body outlet. To rinse the filter, the ball valve is opened
which discharges the dirt particles. A continous supply of
filtered water is available also during the rinse cycle.
3. Application
Medium
Water
The filter is constructed for drinking water installations. In
case of a process water application the filter has to be proven
individually.
4. Technical data
Installation position
Horizontal with filter bowl downwards
Operating pressure
FF06-AA, FF06EA max. 16.0 bar
FF06-AAM max. 25.0 bar
Operating temperature FF06-AA, FF06EA max. 40 °C
FF06-AAM max. 70 °C
Connection size
/
" ,
1
2
5. Scope of delivery
The fine filter comprises:
• Housing with female and male threads
• Threaded connections (version AA)
• Fine filter in clear filter bowl
• Ball valve
• Double wring wrench
6. Options
FF06-...AA =
with clear filter bowl, threaded male connec-
tions, filter mesh size 100 µm
FF06-...EA =
with clear filter bowl, without connections,
filter mesh size 100 µm
FF06-...AAM = with brass filter bowl, threaded male connec-
tions, filter mesh size 100 µm
MU1H-1115GE23 R0609
/
", 1", 1
/
"
3
1
4
4
GB
7. Assembly
7.1 Installations Guidelines
• Install in horizontal pipework with filter bowl downwards
o This position ensures optimum filter efficiency
• Install shutoff valves
• Ensure good access
o Degree of contamination can be seen with clear filter
bowl
o Simplifies maintenance and inspection
• The installation location should be protected against frost
• Fit immediately after water meter
o Corresponds to DIN 1988, Part 2
7.2 Assembly instructions
We recommend to install an inlet check valve (accesso-
ries)
Observe the flow direction when mounting the backflow
preventer.
When connecting the solder sockets, do not solder the
sockets together with the filter. High temperatures
destroy internal parts which are important to the func-
tion!
1. Thoroughly flush pipework
2. Install filter
o Note flow direction
o Install without tension or bending stresses
7.3 Drain for rinse water
The rinse water must be piped to the drain in such a way
that no back pressure can oc-cur
1. Discharge into drain connector
2. Discharge into floor drain
Filter size
Reverse rinsing quantity* C (mm)
1/2" - 1 1/4"
25 litres
*at 4,0 bar inlet pressure and a rinse duration of 15 seconds
8. Maintenance
We recommend a planned maintenance contract with
an installation company
In accordance with DIN 1988, part 8, the following measures
must be taken:
8.1 Inspection
8.1.1 Rinse filter
Frequency: at least every 2 month (depending on local
operating conditions
• Non-compliance can lead to the filter becoming
blocked This results in a drop in pressure and
decreasing water flow
• The filter meshes are made of stainless steel. A red
coating as a consequence of rust from the pipelines
has no influence on function or the way the filter
works
To be carried out by an installation company or the
operator.
Filtered water can be drawn during rinsing.
4