When the remote controls are included for the first time, it is necessary to
erase the list as it is indicated in the section 5f.
Press button ( ) repeatedly until
( ). Point at the selector with the remote control
and hold any button until a number between 1 and 4 flashes on the display.
This value indicates the number of remote controls saved in the list. A
maximum of 4 remote controls can be programmed.
You can only include remote controls with ref.
Press button ( ) repeatedly until
Press again button ( ) rpeatedly until
( ) and the list of authorized remote controls will be deleted.
After completing this process the Optima Selector will not respond to any
remote control.
If the self-diagnostic system detects any malfunction on the performance of the door or in any of the accessories, the selector will alert the end user showing
a numeric code flashing on the display. The list of the malfunction codes are:
Excessive network tension
Short-circuit in motor or
electric circuit
Break-out leaves open
Check bridge between
terminals 10 and 11
(Bravo); 2 and 3 (Activa+)
Obstruction within the leaf
stroke, or motor tension too
low when closing.
Key was not removed
from the cylinder
P a r a m e t e r
(EEPROM) is faulty
Obstruction within the leaf
stroke, or motor tension too
low when opening.
Lock is blocked
Magnetic switch is missing
Infrarred beam is obstructed Clean optics, check if there
The technical specifications described in this manual are given for information purposes
only, and do not represent any contractual obligation for Manusa.
Manusa reserves the right to modify in any moment and without prior notice the technical
specifications displayed in this manual, whenever it is considered to improve the product.
Last revision: December 2006
appears on the display. Then press
then press
in the list.
appears on the display. Then press ( ).
appears on the display. Then press
Verify network tension
Verify motor resistance
(50 Ohm) Bravo
(5,8 Ohm) Activa+
Close break-out leaves
fully and verify magnetic
switch and leaf magnets
Bridge terminals 10 and
11 (Bravo); 2 and 3
(Activa+)
Check eccentric wheels and
floor guides. Increase
closing force and speed.
Remove obstruction
Remove key from the key
switch device
m e m o r y
Replace control
panel.
Check eccentric wheels and
floor guides. Remove
obstruction
Adjust lock
Replace lock
is any cable broken or
shortcircuit.
Press button ( ) repeatedly, until
The display will then show the selected operating mode, or a malfunction
code if there was.
To save the new parameters in memory, change the operating
mode to “OPEN” followed by “AUTOMATIC”
To avoid unwanted manipulations of the selector, you can block the key pad
pressing buttons ( ) and
To unblock again the keypad press button ( ) and
Edif. TESTA-10, 4º
Avda. Vía augusta, 71-73
08174 Sant Gugat del Vallés
Barcelona - España
Tel. +34 902 321 400
Fax +34 902 321 450
EN
M
03
appears on the display. Then press ( ).
simultaneously.
simultanelusly
24 v battery is empty
Verify battery tension
Fail-safe electric circuit
Ub > 27 v
is faulty.
Replace control panel
Radar terminals permanenlty
Check connections.
closed for more than 5 sec.
Replace inside radar
Radar terminals permanenlty
Check connections. Replace
closed for more than 5 sec.
outside radar
Verify that wires are
Selector is not
connected properly
powered
Check power tension (12
Volt) between terminals 1
and 4 on the Selector
Communication with the
C h e c k c o m m u n i c a t i o n
operatror is missing
terminals 2 and 3 on the
Selector.
Polígono Industrial Km. 1,2
43800 Valls - Tarragona (España)
Tel.+34 902 321 700
Fax+34 902 321 750
EMSM03