1
User
The CP field bus node 11 is intended exclusively for use as
a slave on the DeviceNet. The maximum values specified in
the section Technical specifications" must be observed
here.
Detailed information can be found in the manual
P.BE−CP−FB11−E.. .
Warning
S Switch off the power supply before connecting or
disconnecting plugs (otherwise this could lead to
functional damage).
S Use power supplies which guarantee reliable electri
cal isolation of the operating voltage as per IEC/DIN
EN 60204−1. Consider also the general requirements
for PELV circuits in accordance with IEC/DIN EN
60204−1.
S Connect an earth conductor of sufficient cross−sec
tional area to the terminal marked with the earth
symbol.
S Commission only a CP system which has been fitted
and wired completely.
If to be used as an explosion−protected operating de
vice, make sure that:
S electrical contacts are not disconnected under ten
sion
S the completely fitted valve terminal with all plugs,
adapters and protective caps complies at least with
protection class IP 64.
Festo CP−FB11−E 0503f English
instructionsEnglish
13