11
Troubleshooting
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor
unit by checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every DIP switch to OFF after checking.
7-Segment display and check code
Rotary switch setting value
SW01
SW02
SW03
1
1
1
Outdoor unit check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
E06
Number of indoor units which received normally
E07
—
E08
Duplicated indoor addresses
01: Communication between indoor and outdoor units
E12
02: Communication between outdoor units
E15
—
00: Capacity over
E16
01~: Number of connected units
00: Header is nothing
E19
02: 2 or more header units
01: Other line outdoor connected
E20
02: Other line indoor connected
E23
—
E25
—
E26
Number of outdoor units which received normally
E28
Detected outdoor unit No.
E31
IPDU quantity information
(*1)
E31
80
F04
—
F05
—
01: TE1 sensor
F06
02: TE2 sensor
01: TL1 sensor
F07
02: TL2 sensor
03: TL3 sensor
F08
—
01: TG1 sensor
F09
02: TG2 sensor
01: TS1 sensor
F12
03: TS3 sensor
01: Compressor 1
F13
02: Compressor 2
165-EN
1117101201-3 EN.indd 83
1117101201-3 EN.indd 83
D600
D601 D602 D603 D604
Indication
LED
A
B
Outdoor unit number
A
(U
to U
)
1
3
B
Check code display*
Check code name
Decrease of number of indoor units
Indoor/outdoor communication circuit error
Duplication of indoor addresses.
Automatic addressing start error
No indoor unit during automatic addressing
Capacity over / number of connected indoor units
Number of header outdoor unit error
Other lines connected during automatic addressing
Sending error between outdoor units communication
Duplicated follower outdoor address set up
Decrease of connected outdoor units
Follower outdoor unit error
IPDU communication error
Communication error between MCU and sub MCU
TD1 sensor error
TD2 sensor error
TE1 sensor error
TE2 sensor error
TL1,TL2 or TL3 sensor error
TO sensor error
TG1 or TG2 sensor error
TS1 or TS3 sensor error
TH (Heat sink) sensor error
– 83 –
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
F15
—
F16
—
F23
—
F24
—
F31
—
01: Compressor 1
H01
02: Compressor 2
01: Compressor 1
H02
02: Compressor 2
01: Compressor 1
H03
02: Compressor 2
H05
—
H06
—
H07
—
01: TK1 sensor error
02: TK2 sensor error
H08
04: TK4 sensor error
05: TK5 sensor error
H15
—
01: TK1 oil circuit error
02: TK2 oil circuit error
H16
04: TK4 oil circuit error
05: TK5 oil circuit error
L02
Model mismatch of indoor and outdoor unit
L04
—
L06
Number of prior indoor units
L08
—
L10
—
L17
—
L28
—
L29
IPDU number information
(*1)
L30
Detected indoor unit address
L31
—
P03
—
01: Compressor 1
P04
02: Compressor 2
00:
P05
01: Compressor 1
02: Compressor 2
Check code name
Outdoor temp. sensor miswiring (TE1, TL1)
Outdoor pressure sensor miswiring (Pd, Ps)
Ps sensor error
Pd sensor error
Outdoor EEPROM error
Compressor breaking down
Compressor error (Locked)
Current detection circuit error
TD1 sensor miswiring
Low pressure protective operation
Oil level down detection
Temperature sensor error for oil level
TD2 sensor miswiring
Oil level detector circuit error
System shutdown error from indoor unit
Outdoor system address duplication
Duplication of indoor units with priority
Indoor unit group/address unset
Outdoor unit capacity unset.
Inconsistent models of outdoor units
Outdoor connected quantity over
IPDU quantity error
External interlock of indoor unit
Other compressor errors
Discharge temperature TD1 error
High-pressure SW system operation
Phase missing detection/Phase order error
Compressor Vdc error
166-EN