DUCTED COMBUSTION AIR INTAKE APPLICATIONS
The "Ducted combustion air intake kit" allows ducting of external air directly into the burner.
A 4" diameter air intake is provided in the kit.
This kit is only suitable for connection of combustion air and not suitable for direct vent application.
To mount this kit on the burner, please follow the installation description given in the kit instruction
ATTENTION
sheet.
ONLY FOR F10 - F15 - F20 BURNER:
use a 4" to 6" pipe adapter (not supplied in the kit) to use a 6" diameter pipe.
NOTES:
-
This kit is not suitable for direct vent applications.
-
Always try to minimize the length of the air intake pipe.
-
Reduce pipe length by 10 feet for every 90° elbow, 5 feet for every 45° elbow.
-
Reduce pipe length by 6 feet for the 4" to 6" pipe adapter (ONLY FOR F10 - F15 - F20 BURNER)
-
Air intake venting should be insulated 10 feet from air intake source with a minimum R7 foil lined insulation, to prevent
condensation or corrosion of air intake venting.
-
Use an approved type of air intake vacuum breaker and install it in the same room of the burner. This device should be
tested to prove that the vacuum breaker balancer is set correctly and, in the event of intake air source being blocked,
can provide enough combustion air for the burner. If the room where the burner is installed cannot provide enough air or
air quality is a concern, an additional air inlet source must be provided to this room.
-
On the outside of the wall, use an approved intake air hood, located above the snow line and in such way as to prevent
leaves and/or other debris from blocking the air flow. Refer to local codes for proper location of inlet.
The settings of the burner must be according to the BURNER SETUP CHART – AIR INTAKE APPLICATIONS below.
MODEL F3 BURNER SETUP CHART with 4" diameter pipe
Actual
Nozzle
firing rate
size
GPH
0.50
0.40 x 60°/80°
0.60
0.50 x 60°/80°
0.75
0.60 x 60°/80°
0.80
0.65 x 60°/80°
0.95
0.75 x 60°/80°
MODEL F5 BURNER SETUP CHART with 4" diameter pipe
Actual
Nozzle
firing rate
size
GPH
0.75
0.60 x 60°/80°
0.80
0.65 x 60°/80°
0.90
0.75 x 60°/80°
1.00
0.85 x 60°/80°
1.20
1.00 x 60°/80°
1.30
1.10 x 60°/80°
1.50
1.25 x 60°/80°
1.65
1.35 x 60°/80°
3436
Pump
Head
pressure
setting
PSI
155
0.0
150
0.5
150
1.5
150
2.0
160
3.0
Pump
Head
pressure
setting
PSI
155
0.0
150
0.5
145
1.0
140
1.5
145
2.0
140
2.5
145
3.0
150
4.0
2
20 Ft.
50 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.00
2.00
2.20
2.20
3.40
3.40
3.50
3.50
4.80
4.80
20 Ft.
50 Ft.
pipe length
pipe length
Air Setting
Air Setting
1.60
1.60
1.62
1.62
2.00
2.00
2.25
2.25
3.00
3.00
3.25
3.25
4.50
4.50
5.10
5.10
80 Ft.
100 Ft.
pipe length
pipe length
Air Setting
Air Setting
2.10
2.10
2.30
2.30
3.50
3.50
3.60
3.80
5.50
6.00
80 Ft.
100 Ft.
pipe length
pipe length
Air Setting
Air Setting
1.70
1.75
1.74
1.80
2.00
2.10
2.25
2.50
3.00
3.25
3.25
3.50
5.00
5.75
5.75
6.00