10. Detailed settings / 11. Instrument information
10.8.2 Alarm signal via HART
EN
The instrument status will be set to "Diaphragm rupture".
10.8.3 Alarm signal via current loop
The output residual current can be set to 2 values
3.5 mA = alarm signal downscale
21.5 mA = alarm signal upscale
The factory setting is 3.5 mA.
See chapter 10.3 "Setting the alarm signal" to change the customer-specific presetting.

11. Instrument information

11.1 Displaying measuring range

1. Open the operating menu with [↵].
Select "Info" and confirm with [↵].
2. Select "Measuring range" and confirm with [↵].
» Measuring range is displayed.
50
communication
WIKA operating instructions, model DMSU21A