9.11. SE2 (Opening)
In this menu item you can set whether the controller is to monitor the
safety input SE2 (terminal 33) for an 8.2kΩ resistor (safety contact strip)
or for an OES strip (optoelectronic safety contact strip).
x 8k2
x OES
Furthermore, the effect of actuating the safety input must be selected
(only effective when closing!):
x NO Effect
x Stop
x Disengage (ca. 1 sec)
x Reverse
9.12. SE-Standby
This menu item allows you to set whether the board cuts off the 12V
power supply of the optoelectronic safety edge (Terminals 31 & 34) at
gate standstill in order to save energy.
(This function is only necessary in battery mode):
NO Standby
x
Standby
x
9.13. Stop
This menu item is for informative purposes only(!), you can see whether
the stop is open <active> or closed <OK>.
9.14. Warning light
In this menu item, you can set whether and for how long the warning light
(terminals 7 & 8) lights up (0-10 seconds) before closing and before
Opening, except for setting end position indication.
Warning X-X
Output „flashes".
Warning XXX
Output permanent signal.
End position
Output is activated as soon as an end position is
reached.
End position
Output activates as soon as an end position Open is
OPEN
reached.
End position
Output activates as soon as an end position Closed is
CLOSED
reached.
It can be tested with the buttons<+> and <->.
27