Speed; Soft Start; Soft-Run Opening; Soft Run Closing - BelFox 47-21-i Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

9.19. Speed

In this menu item you can individually set the speed, at which the gate
runs "OPEN" or "CLOSED". This is a percentage voltage setting, so the
setting is not completely linear.

9.20. Soft start

In this menu item you can set the speed at which the drive always starts;
the duration of the soft start can also be set here.

9.21. Soft-run OPENING

For safety reasons, a minimum run-out distance of 60cm must be pro-
grammed! This corresponds to the percentages given in the table under
point 9.22.
In this menu item you can set the speed, at which the drive in the soft
stop direction OPEN will run out, and the length of the soft stop can also
be set here proportionally.

9.22. Soft run CLOSING

For safety reasons, a minimum run-out distance of 60cm must be pro-
grammed! This corresponds to the percentages given in the table below.
In this menu item you can set the speed at which the drive in the soft stop
direction CLOSE runs out, and the length of the soft stop can also be set
here as a percentage.
IS* at the opening in m
Min. length of smooth run 60% 30%
IS* at the opening in m
Min. length of smooth run
*IS = Intermediate space
CAUTION!
CAUTION!
1
2
3
20%
15%
10
11
12
6%
5%
5%
5%
30
4
5
6
12%
10%
9%
13
14
15
16
4%
4%
4%
7
8
9
8%
7%
17
>17
4%
4%