CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units
except any one of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-3)
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting. (Fig. 4-4)
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches that are less than 1 m are not included in the total branch number.) (Fig. 4-5)
Branch
Point
16 or fewer
(5) Use shielded wires for inter-unit control wiring (c) and
ground the shield on both sides, otherwise misoperation
from noise may occur. (Fig. 4-6)
Connect wiring as shown in Section "4-3. Wiring System
Diagrams".
Shielded wire
(Functional earthing)
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
NO
NO
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
more than 1 m
Indoor unit
Indoor unit
more than 1 m
Indoor unit
less than 1 m
Indoor unit
(Functional earthing)
Fig. 4-6
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch point
Outdoor unit
Indoor unit
Indoor unit
(6) • Connecting cable between indoor unit and outdoor
unit shall be approved polychloroprene sheathed 5 or
3 *1.5 mm
fl exible cord. Type designation 60245 IEC57
2
(H05RN-F, GP85PCP etc.) or heavier cord.
• Use the standard power supply cables for Europe (such
as H05RN-F or H07RN-F which conform to CENELEC
(HAR) rating specifi cations) or use the cables based on
IEC standard. (60245 IEC57, 60245 IEC66)
WARNING
Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also occur. Therefore,
ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the
instructions on "How to connect wiring to the terminal" and fasten
the wire securely with the terminal screw.
21
Prohibited
Indoor unit
Fig. 4-3
Fig. 4-4
Outdoor unit
Indoor unit
Indoor unit
Fig. 4-5