ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Made in Czech Republic
02-16/2018 Rev.: 0
Characteristics
• The Universal input is used to detect device statuses which ensure the smooth and
trouble-free operation both in the residential and industrial sectors.
• The Universal input has a pulse, analog, binary input and terminals for connecting
the temperature sensor.
• In conjunction with the sensor it is used, for example, for monitoring the level, tem-
perature, gas, water or electricity, fl ooding...
• It provides a quick solution to learn about the critical condition of your device which
you can immediately respond to (e.g. service interference).
• Using the universal sensor will help you eliminate fi nancial losses caused by device
malfunctions, or report the need for action in advance.
• For each power meter it is necessary to have one Universal input AirIM-100.
• With the wireless solution and Sigfox / LoRa / NB-IoT communication, it can com-
municate instantly to your chosen location and be operated immediately.
• Data is sent to the server from which it can be subsequently displayed as a smart-
phone, application, or Cloud notifi cation
• Anti-sabotage: If access to the device is unauthorized, a message is immediately
sent to the server.
• Anti-sabotage: When a cover is removed, a message is sent to the application or
ELKO Cloud.
• Power supply: 5-12 V DC or 1x 3.6 V batteries SAFT with approx. 5 years (depending
on the frequency of use)
• In the case of external power, the battery is automatically disconnected and serves
as backup power.
• Protection degree IP65.
Description
1
2
13
4
5
+ -
6
7
Cloud app assignment
It is done in your Smartphone application. Enter the relevant information on the product
cover into the application.
Set the sensing type (sensor LS, WS, MS or pulse output S0).
1. Tamper
8
2. NanoSIM slot (AirIM-100NB only)
6
3. LED indication
4. Button SET
9
5. Setting pins for 3V3 / GND clamp
6. Hole for mounting on the wall
Ø 4.3 mm / 0.2"
10
3
7. Power terminal
14
8. Antenna
15
9. Magnetic contact
11
10. Battery
11. Sensor connection terminal
12
12. Bushing M16x1.5 for connecting
cable with max. diameter of 10 mm
13. Programming pins
14. Setting pins for CH2 clamp
15. Setting pins for CH1 clamp
AirIM-100
Universal input
General instrucions
Internet of Things (IoT)
• The IOT wireless communications category describes the Low Power Wide Area
(LPWA). This technology is designed to provide full-range coverage both inside and
outside buildings, energy-saving and low-cost operation of individual devices. Indivi-
dual networks - Sigfox, LoRa, NarrowBand - are available to use this standard.
Sigfox network information
• The network supports bidirectional communication but with a limited number of feed-
backs. It uses the free frequency band divided by Radio Frequency Zones (RCZ).
•
RCZ1 (868 MHz) Europe, Oman, South Africa
•
RCZ2 (902 MHz) North America
•
RCZ3 (923 MHz) Japan
•
RCZ4 (920 MHz) South America, Australia, New Zealand, Singapore, Taiwan
• Sigfox has more coverage across countries, so it is better suited for long distance mo-
nitoring.
• For more information on this technology, please visit www.sigfox.com.
LoRa network information
• The network is bidirectional and its communication uses free frequency band.
•
865 - 867 MHz
•
867 - 869 MHz
•
902 - 928 MHz
• The advantage of this network is the possibility of freely deploying individual stations
in local locations, thus strengthening their signal. It can therefore be used effi ciently in
company premises or, for example, in local parts of cities.
• For more information on this technology, please visit www.lora-alliance.org.
Information about the NarrowBand network
• The network provides two-way communication and the only one to use the licensed
LTE band. Our devices allow band 1 (2100MHz), Band 3 (1800MHz), Band 8 (900MHz),
Band 5 (850MHz), Band 20 (800MHz) and Band 28 (700MHz).
• It uses this SIM card technology for each device.
• The advantage of NarrowBand is the use of already built-up grids, which ensures suffi -
cient reception outside and inside buildings.
• For more information on this technology, please visit www.vodafone.cz
Caution for proper operation:
• Products are installed according to the wiring diagram given for each product.
• For proper device functionality, it is necessary to have suffi cient coverage of the selec-
ted network at the installation site.
• At the same time, the device must be registered in the network. Successful device re-
gistration on a given network requires a charge for traffi c.
• Each network off ers diff erent tariff options - it always depends on the number of me-
ssages you want to send from your device. Information on these tariff s can be found in
the current version of the ELKO EP pricelist.
1 / 4
India
Europe
North America, Japan, Korea
EN