2.1 CIM 1XX LON module
1 2 3
Fig. 1
CIM 1XX LON module
Pos.
Designation Description
1
A
2
B
3
Screen
4
LED1
5
Pin
6
LED2
4
5
6
LON terminal A
LON terminal B
LON terminal for cable
screen
Yellow service LED
Service pin (push-button)
Red/green status LED for
internal communication
between the CIM 1XX and
the Grundfos product
3. Installation
Warning
The CIM 1XX must only be connected to
SELV or SELV-E circuits.
3.1 Connecting the LON
Grundfos recommends to use a cable according to
Echelon standards.
Examples of recommended cable types
•
Belden 85102
•
Belden 8471
•
Level IV, 22 AWG
•
JY(St) Y 2 x 2 x 0.8
•
TIA Category 5.
A LON network must be terminated. The termination
depends on the network topology chosen.
Fitting the cable
Procedure:
See fig. 2.
1. Connect the conductors to terminal A (pos. 1).
2. Connect the conductors to terminal B (pos. 2).
3. Connect the twisted screen ends to terminal
"Screen" (pos. 3).
The screen must only be connected to the
screen terminal of the CIM 1XX LON
module. See fig. 2, pos. 3.
Note
The cable screen must never be
connected to earth via the earth clamp.
See fig. 2, pos. 4.
The stripped part of the cable screen must
Note
be as short as possible to reduce the
impedance at high frequencies.
3
2
1
4
Fig. 2
Connecting the LON
Pos.
Description
1
LON terminal A
2
LON terminal B
3
LON terminal for cable screen
4
Earth clamp
5