1. General
The Flamco Clean Smart dirt separator is intended for heating and cooling systems with water
(Glycol maximum 50%).
Flamco Clean Smart complies with the Pressure Equipment Directive, 2014/68/EC (Cat. I - IV).
The Flamco Clean Smart may be hot during operation.
Minimum and maximum system temperature:
Minimum and maximum system pressure:
Maximum flow velocity:
Safety requirements
This product contains a powerful magnet. Care must be taken in the vicinity of pacemakers, data
carriers and other products that are sensitive to magnetism.
Installation and maintenance must be carried out by qualified personnel only.
Observe local regulations and guidelines.
2. Installation
Do not install the product above a suspended ceiling or in the vicinity of electronic installations!
Install the Flamco Clean Smart in a dry location not susceptible to frost and which is easily
accessible for maintenance purposes. Flush the installation thoroughly before installing the
Flamco Clean Smart.
For optimum efficiency, the connection diameter of the Flamco Clean Smart must correspond to
the pipe diameter of the system. It is further recommended that the inlet pipe into the device be a
straight pipe having a length of no less than 5 times the nominal pipe diameter. Always install the
product perpendicular (air vent at bottom) (fig. 1). Install the Flamco Clean Smart in the direction
of flow in accordance with the arrow shown on the connection.
Install the Flamco Clean Smart directly before the boiler in the return line, preferably before the
circulation pump (fig. 2A, 2B, 2C, 2D).

3. Inspection and maintenance

Perform regular visual inspections.
The dirt that collects at the bottom of the Flamco Clean Smart can be removed with the aid of the
drain valve (fig. 5). Before draining, rotate the scraper and remove the magnet (fig. 3, 4 and 5)
open the drain valve and let it wash way dirt. Close the drain valve and place the magnet back
A hose can be attached to the drain valve as required. Only use the drain valve for draining dirty
system water, never for filling or draining the installation (fig. 6).
Use the Flamco service stickers to record dates of maintenance on the handle of the drain valve
(fig. 7).
Only carry out maintenance when the system has cooled down, remembering to take account of
the pressure.
4. Dismantling
Depressurise the cooled system and remove the Flamco Clean Smart from the system.
Observe local regulations for disposing of the various parts of the Flamco Clean Smart.