Tripp-Lite SmartOnline Manual Del Usuario página 6

Ocultar thumbs Ver también para SmartOnline:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
3
EPO Port Connection
This optional feature is only for those
applications that require connection to a
facility's Emergency Power Off (EPO) circuit.
When the UPS is connected to this circuit, it
enables emergency shutdown of the UPS's
inverter and inhibits transfer to internal bypass.
Using the cable provided, connect the EPO port
3a
of your UPS (see
) to a user-supplied
normally closed or normally open switch
according to the circuit diagram (see
Note:
1. If using a cable other than what is supplied, the
cable should not exceed 350 feet or have a
resistance of greater than 10 ohms.
2. If a non-latching EPO switch is used, the EPO must
be held for a minimum of 1 second. This does not
apply to a latching EPO switch.
CAUTION: The EPO port is not a phone line
surge suppressor; do not connect a phone
line to this port.
UPS Unit State when asserting EPO with AC line present:
LEDs
OFF
To restart the UPS unit after asserting EPO with AC line present:
Option 1:
1. Verify that the EPO assertion has been removed or cleared.
2. Press OFF button until you hear a click (approx. 1 second).
3. Press ON button and UPS output will turn back on.
Option 2:
1. Verify that the EPO assertion has been removed or cleared.
2. Remove AC line power to the UPS unit.
3. Reapply AC line power. Now the UPS will start back up in normal operation mode.
UPS Unit State when asserting EPO without AC line power:
LEDs
OFF
To restart the UPS unit after asserting EPO without AC line power:
1. Verify that the EPO assertion has been removed or cleared.
2. Reapply AC line power to the UPS unit. Now the UPS will start back up in normal operation
mode.
201102199 93-2471.indb 6
3b
).
Output
Fans
OFF
ON
Output
Fans
OFF
OFF
Your model may differ.
3a
3b
Serial
SNMP
ON
Serial
SNMP
OFF
6
4-5
USB
ON
ON
USB
OFF
OFF
3/30/2011 9:14:01 AM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Su1000rtxl2uaSu1000xlaSu1500xlSu3000xl

Tabla de contenido