Appendix A
A.1
I/O Connections and Wiring
Terminal Block Wiring - 1010DXS2-7
(Refer to manual drawing 1010DXS2-7 sheet 3 of 4. When Barriers are used, isolation is
limited to the Barrier's working voltage. Refer to table on manual drawing 1010-341 sheet 3).
These connection diagrams apply to the part numbers listed below.
Table A- 1
FUG1010
Table A- 2
Pin#
SITRANS FUG1010 Quick Start
Operating Instructions (Compact), 1/2009, CQO:QSG005 Revision B
Part Numbers and Connection Diagrams
FUG1010 Input/Output Wiring (TB1)
Signal
1
Io2-
Isolated Loop Return
2
Io2+
Isolated Loop Supply
3
Io1 -
Isolated Loop Return
4
Io1 +
Isolated Loop Supply
5
ANIN 2
4-20mA Input CH. 2
6
ANIN 1
4-20mA Input CH.1
7
Status -1
Status Bit Return
8
Status +1
Status Output
9
Status -2 -
Status Bit Return
10
Status +2
Status Output
1010DXS2-7 (Sheet 3 of 4) Drawing
7ME3611a-bc
where:
b= 1
c= D
Function
Spannable 4-20mA output proportional to any
available data variable assigned under menu
control
4-20mA input non-isolated)
CH. 1 Status Alarm Emiter
CH. 1 Status Alarm Collector
CH. 2 Status Alarm Emiter
CH. 2 Status Alarm Collector
A
Description
39