Daikin EWYQ F Serie Manual De Instalación, Operación Y Mantenimiento página 14

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 48
Fig. 4A
Fig. 4C
Fig. 4E
Fig. 4G
7. A filter or device that can remove particles from the fluid.
The use of a filter extends the life of the evaporator and
pump and helps to keep the water system in a better
condition.
8. Evaporator has an electrical resistance with a thermostat
that ensures protection against water freezing at ambient
temperatures as low as –25°C. All the other water
piping/devices outside the unit must therefore be protected
against freezing.
Figure 4 - Minimum clearance requirements
Fig. 4B
Fig. 4D
Fig. 4F
Fig. 4H
9. The heat recovery device must be emptied of water during
the winter season, unless an ethylene glycol mixture in
appropriate percentage is added to the water circuit.
10. If case of unit substitution, the entire water system must be
emptied and cleaned before the new unit is installed.
Regular tests and proper chemical treatment of water are
recommended before starting up the new unit.
11. In the event that glycol is added to the water system as
anti-freeze protection, pay attention to the fact that suction
D-EIMHP00604-14EU - 14/208

Publicidad

Tabla de contenido
loading

Tabla de contenido