Tabla De Contenido; Introduction - Panasonic Urban Multi U-8ME4XPQ Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 107
U-8ME4XPQ
U-14ME4XPQ
U-10ME4XPQ
U-16ME4XPQ
U-12ME4XPQ
C
ONTENTS
1. Introduction ................................................................................1
1.1. Indoor capacity range .................................................................. 2
1.2. Standard supplied accessories.................................................... 2
1.3. Optional accessories ................................................................... 2
1.4. Technical and Electrical specifications......................................... 2
2. Main components.......................................................................2
3. Selection of location ...................................................................3
4. Inspecting and handling the unit ................................................4
5. Unpacking and placing the unit ..................................................4
6. Refrigerant piping.......................................................................4
6.1. Installation tools ........................................................................... 5
6.2. Selection of piping material.......................................................... 5
6.3. Pipe connection ........................................................................... 5
6.4. Connecting the refrigerant piping................................................. 5
6.6. Example of connection ................................................................ 7
7. Leak test and vacuum drying .....................................................9
8. Field wiring .................................................................................9
8.1. Internal wiring - Parts table ....................................................... 10
8.2. Optional parts connector ........................................................... 10
8.3. Power circuit and cable requirements ........................................ 11
8.4. General cautions........................................................................ 11
8.5. System examples ...................................................................... 11
8.6. Leading power line and transmission line .................................. 12
8.7. Field line connection: transmission wiring.................................. 12
8.8. Field line connection: power wiring ............................................ 13
8.9. Wiring example for wiring inside unit ......................................... 14
9. Pipe insulation..........................................................................14
10. Checking of unit and installation conditions .............................14
11. Charging refrigerant .................................................................15
11.2. Precautions when adding R410A .............................................. 15
11.3. Stop valve operation procedure ................................................. 15
11.5. Additional refrigerant charge...................................................... 16
charge weight into the PCB ....................................................... 19
11.7. Checks after adding refrigerant ................................................. 20
12. Before operation.......................................................................20
12.1. Service precautions ................................................................... 20
12.2. Checks before initial start-up ..................................................... 21
12.3. Field setting ............................................................................... 21
12.4. Test operation ............................................................................ 23
12.5. Final check after installation ...................................................... 24
13. Service mode operation ...........................................................25
14. Additional refrigerant charging method ....................................25
15. Caution for refrigerant leaks.....................................................26
16. Disposal requirements .............................................................26
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
IMPROPER
INSTALLATION
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY PANASONIC WHICH
ARE SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
PANASONIC
EQUIPMENT
COMFORT APPLICATIONS. FOR USE IN OTHER
APPLICATIONS, PLEASE CONTACT YOUR LOCAL
PANASONIC DEALER.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DEALER FOR ADVICE AND
INFORMATION.
THIS AIR CONDITIONER COMES UNDER THE TERM
"APPLIANCES NOT ACCESSIBLE TO THE GENERAL
PUBLIC".
U-8~16ME4XPQ
Urban Multi air conditioner
4PW40726-1A
Urban Multi air conditioner
Page
OR
ATTACHMENT
OF
IS
DESIGNED
FOR
The refrigerant R410A requires strict cautions for keeping
the system clean, dry and tight.
Clean and dry
Foreign materials (including mineral oils such as
SUNISO oil or moisture) should be prevented from
getting mixed into the system.
Tight
R410A does not contain any chlorine, does not
destroy the ozone layer and does not reduce the
earth's protection against harmful ultraviolet radiation.
R410A can contribute slightly to the greenhouse
effect if it is released. Therefore we should take
special attention to check the tightness of the
installation.
Read "6. Refrigerant piping" on page 4 carefully and follow
these procedures correctly.
Since design pressure is 4.0 MPa or 40 bar (for R407C
units: 3.3 MPa or 33 bar), pipes of larger wall thickness
may be required. The wall thickness of piping must be
carefully selected, refer to paragraph "6.2. Selection of
piping material" on page 5 for more details.
1.
I
NTRODUCTION
This installation manual concerns Urban Multi inverters of the Panasonic
U-ME4XPQ series. These units are designed for outdoor installation and
used for cooling and heat pump applications. The U-8~16ME4XPQ
system is a single outdoor system and can not be combined with other
outdoor units in a multi outdoor system. This unit has rated cooling
capacities ranging from 22.4 to 45.0 kW and rated heating capacities
ranging from 25.0 to 50.0 kW.
For changing the refrigerant flow to indoor units, the U-ME4XPQ
system can be combined with HR units of the types CZ-100HR1HS,
CZ-160HR1HS and CZ-250HR1HS only. Other HR unit types will
cause malfunctions when combined with the U-ME4XPQ system.
The U-ME4XPQ units can be combined with Panasonic Urban Multi
indoor units for air conditioning purposes suitable for R410A.
The present installation manual describes the procedures for
unpacking, installing and connecting the U-ME4XPQ units.
Installation of the indoor units is not described in this manual. Always
refer to the installation manual supplied with these units for their
installation.
Installation manual
Installation manual
1

Publicidad

Tabla de contenido
loading

Tabla de contenido