For compliance with the protection objectives
of the German EMC Act (EMVG) in systems and
machines, the following EMC standards must
be satisfied:
Product Standard EN 61800-3
EMC standard for drive systems (PowerDrive-
System), interference immunity and emissions
in residential areas, enterprise zones with light
industry and in industrial facilities.
This standard must be complied with in the EU
for satisfying the EMC requirements for systems
and machines!
Second environment (industry) with PDS categories C3, C4
satisfied
PDS category C3
Medium-voltage network
Supply transformer for a
Industrial zone
residential area (rating
normally
≤
1.2 MVA)
Earthed
neutral
Earthed 400-V network
with neutral conductor ;
3~
≤
400 A
Mains filter
Line reactor +
Line reactor
Line reactor
Y-capacitor
Converter
Converter
Converter
M
M
M
M
M
Operation at low-voltage network together with
other loads of all kinds, apart from some kinds
of sensitive communication equipment.
For emitted interference, the following apply:
EN 61000-6-3 Specialised basic standard for emissions in light industry
EN 61000-6-4 Specialised basic standard for emissions in industry
For interference immunity, the following apply:
EN 61000-6-1 Specialised basic standard for interference immunity in
EN 61000-6-2 Specialised basic standard for interference immunity in in-
* The generic standards are given in brackets
Not applicable
on customer's request
satisfied
PDS category C4
Industrial
zone
Converter
transformer
Converter
M
M
Operation with separate power converter transformer. If there
are other loads at the same secondary winding, these must be
able to cope with the commutation gaps caused by the power
converter. In some cases, commutating reactors will be
required.
can be satisfied with special features (mains filters, screened
power cables) in the lower rating range *(EN 50081-1).
*(EN 50081-)
residential areas *(EN 5008-1)
dustry. If this standard is satisfied, then the EN 61000-6-1
standard is automatically satisfied as well *(EN 5008-).
satisfied
Medium-voltage network
Converter
transformer
with earthed
iron core
(and earthed
I > 400 A
screen where
and/or
appropriate)
U > 500 V
Line reactor
Converter
M
M
M
3ADW000191R0500 DCS800 Quick guide edisf e
Standards
EN 61800-3
EN 61000-6/3
EN 61000-6/3
EN 61000-6-2
EN 61000-6-1
Classification
The following overview utilises the
terminology and indicates the ac-
tion required in accordance with
Product Standard
EN 61800-3
For the DCS800 series, the limit
values for emitted interference
are complied with, provided the
measure indicated is carried
out. PDS of category C (for-
merly restricted distribution in
first environment) is intended to
be installed and commissioned
only by a professional (person
or organization with necessary
skills in installing and/or com-
missioning PDS including their
EMC aspects).
For power converters without
additional components, the fol-
lowing warning applies:
This is a product of category C
under IEC 61800-3:004. In a
domestic/residential environment
this product may cause radio
interference in which case sup-
plementary mitigation measures
my be required.
The field supply is not depicted
in this overview diagram. For the
field current cables, the same
rules apply as for the armature-
circuit cables.