Regular Maintenance Recording Form; Expansion Vessel - Carel WTS compact Manual Del Usuario

Instalación de ósmosis inversa con bomba
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ENG

6. REGULAR MAINTENANCE RECORDING FORM

Model: WTS Compact
Regular maintenance recording form
Values to be measured on the spot
Conductivity at the inlet
Decay quantity

Expansion vessel

Spare parts
Micrometric fi lter
Feed water
pressure
Water pressure
downstream of the
fi lter
If pressure drop > 1 bar
IMMEDIATELY REPLACE THE FILTER or REPLACE EVERY YEAR
Date of last fi lter replacement:
Osmotic membrane
Replacement recommended when the conductivity value
of the permeate or the permeate fl ow rate value is not
satisfactory any more
Regular replacement recommended once every two years.
Date of last membrane replacement:
Various remarks
N.
Date
"osmosi inversa" +0300017IE rel. 1.4 - 05.04.2018
Serial number
(to be fi lled in with a monthly interval)
Conductivity at the outlet
Drain quantity
Stop pressure (default 4 bar)
Start pressure (default 2 bar)
Person in charge
18
Date of fi rst start-up
Pump working pressure
(default from 5 to 10 bar)
Recovery value
permeate / (permeate+drain) = about 40-60%
Air precharge pressure (default 1.8 bar)
To measure the precharge pressure, it is
advisable to drain the vessel and use a pressure
gauge to measure the air residual pressure
in the same vessel. It is advisable to perform
this operation every month, to guarantee the
hygiene of the stored water.
Micrometric fi lter
Quantity of free chlo-
rine in the feed water
If < 0.1 replace 3 months
0.1< If < 0.2 replace 2 months
Date of last fi lter replacement:
UV light (optional)
The UV light should be replaced every 10000 hours of opera-
tion (about once a year).
Date of last UV light replacement:
The removal and cleaning of quartz is recommended ap-
proximately every 6 months
Date of last UV/quartz light cleaning:
Signature