HEAT DISPERSAL
The inverter generates heat while it is working. This is not a malfunction. However,
if the inverter gets too hot while working, it will turn off by itself. Position the
inverter where air flows freely around it to allow the heat to disperse. The inverter's
thermal protection prevents it from operating when its temperature exceeds
130ºF ± 10ºF.

TROUBLESHOOTING

PROBLEM: Low or No Output Voltage – Fault LED Lit
Reason
Poor contact with battery or inverter
terminals.
PROBLEM: Inverter Automatically Shut Down – Fault LED Lit
Reason
Battery voltage below 10V
Inverter is too hot.
(Thermal protection mode.)
Unit may be defective.
Equipment being operated draws too
much power.
PROBLEM: Pulsing Alarm
Reason
Input voltage below 10.5V
Poor or weak battery condition.
Poor or loose cable connection.
Inadequate power being delivered to
the inverter or excessive voltage drop.
Wagan Tech and wagan.com are trademarks used by Wagan Corporation.
User's Manual—Read before using this equipment
©2017 Wagan Corporation. All Rights Reserved.
Solution
Clean terminals thoroughly. Reinstall
and tighten.
Solution
Charge or replace battery.
Allow inverter to cool.
Check for adequate ventilation.
Reduce the load on the inverter to
rated continuous power output.
See warranty and call customer service.
Use a higher capacity inverter or do
not use this equipment.
Solution
Keep input voltage above 10.5V
Recharge or replace battery.
Inspect terminals and tighten all
connections.
Use heavier gauge DC cable.
Keep cable length as short as possible.
10