Descargar Imprimir esta página

Daikin DWME Manual Del Usuario página 9

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 36
Operating Limits
The units are designed for indoor, non-freezing locations. Outdoor locations will require special design considerations.
Note:
Min. ECWT(° C) = 2,92+(ELWT)-0.75*DT
Where:
ECWT = Entering condenser water temperature
ELWT = Leaving chilled water temperature
DT
= Chilled Water Delta-T at full load
FL
PLD = The percent chiller load point to be checked
For example, at 7° C ELWT, 5° C
Label Identification
1 – Manufacturer's logo
2 – Refrigerant type
3 – Non flammable gas symbol
4 – Emergency stop
5 – Hazardous Voltage warning
Table 1 - Operating Parameters
Leaving chilled water (ice duty not available)
Max. operating evaporator inlet fluid temperature
Max. startup evaporator inlet fluid temperature
Max. standby inlet fluid temperature
Min. condenser water entering temperature
Max. leaving condenser water temperature
*(PLD/100)+7,78*(PLD/100)
FL
t @ full load, the entering condenser water temperature could be as low as 10° C.
Figure 1 - Description of the labels applied to the electrical panel
38° F to 60° F
(3.3° C to 15° C)
66° F (19° C)
90° F (32° C)
105° F (46° C )
See note below
105° F (46° C)
2
6 – Electrical hazard symbol
7 – Cable tightening warning
8 – Unit nameplate data
9 – Lifting instructions
D - EIMWC01104-12EU - 9/148

Publicidad

loading