13 - BUS FOR CONNECTION TO AN RS485 MODBUS CMS
■ Bit composition
- Function 1 or 2 is used for reading
- Function 5 or 15 is used for writing
Register No. Description
1
P706 control type
16
P330 supply air fan operation
17
P300 compressor 1 operation
18
P304 compressor 2 operation
19
P320 stage 1 electric heater operation
20
P322 stage 2 electric heater operation
32
P279 start-up request
33
P287 Hot water coil or electric heater contact
34
P288 Summer or winter mode contact
48
P350 critical fault summary
49
P352 non-critical fault summary
50
Supply air fan fault
51
Air flow fault
52
Filter fouled fault
53
Clogged filter fault
55
Electric heater fault
56
Humidifier fault
57
Water leak fault
58
Condensation unit 1 fault
59
Condensation unit 2 fault
60
High temperature fault
61
Low temperature fault
62
High humidity fault
63
Low humidity fault
64
Controlled temperature sensor fault
65
Outlet temperature sensor fault
66
Outdoor temperature sensor fault
67
Brine temperature sensor fault
68
EEPROM fault
70
Humidifier connection fault
71
FMA1 connection fault
72
FMA2 connection fault
73
FMA3 connection fault
74
Update fault with the temperature value controlled by Modbus
75
Controlled temperature sensor fault (2-10 V)
76
2-10 V control signal fault
80
Low pressure fault circuit 1
81
High pressure or circuit 1 break fault
96
Low pressure fault circuit 2
97
High pressure or circuit 2 break fault
112
FMA1 fault summary
128
FMA2 fault summary
144
FMA3 fault summary
512
On/Off
Format
Type
Unit
0 = Local
Binary
R
1 = Remote
0 = Off
Binary
R
1 = On
0 = Off
Binary
R
1 = On
0 = Off
Binary
R
1 = On
0 = Off
Binary
R
1 = On
0 = Off
Binary
R
1 = On
0 = Open
Binary
R
1 = Closed
0 = Open
Binary
R
1 = Closed
0 = Open
Binary
R
1 = Closed
0 = Inactive
Binary
R
1 = Active
0 = Inactive
Binary
R
1 = Active
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
Binary
R
1 = Fault
0 = Off
Binary
R/W
1 = On
73