Electrical Wiring

Dipswitch Setting

The dip-switch is dialled to "On" position with the over-line at the state of strapping if the code or over-line status is "1" The
dip-switch is dialled to "Off'' position with the over-line at the state of disconnection if the code or over-line status is "O".
In the table below, the choice in the box " refers to the setting of the socket/over-line before delivery.
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SWO1 is used to set the capabilities of the master and slave indoor units as well as the indoor unit; SW03 is used to
set the address of the indoor unit (combine original communication address and address of centralized controller).
(A) Definition and description of SW01
Address of
SW01_1
wire
SW01_2
controlled
SW01_3
indoor unit
SW01_4
(group
address)
SW01_5
SW01_6
Capability of
SW01_7
indoor unit
SW01_8
Note 1: A wired controller can connected to at most 16 ultrathin air-duct indoor units.
[1]
[2]
[3]
[4]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
...
...
.. .
.. .
1
1
1
1
[5]
[6]
[7]
[8]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
Address of wire controlled indoor unit (group address)
0# (wire-controlled master unit) (default)
1# (wire-controlled slave unit)
2# (wire-controlled slave unit)
3# (wire-controlled slave unit)
15# (wire-controlled slave unit)
Capability of indoor unit
19
0.6HP
0.8HP
1.0HP
1.2HP
1.5HP
1.7HP
2.0HP
2.5HP
3.0HP
3.2HP
4.0HP
5.0HP
6.0HP
8.0HP
10.0HP
15.0HP