1.
Identify the DC output wires on the battery charger and crimp
spade lugs onto both the positive and negative lead (pur-
chased or supplied separately) (see Figure 1.1).
2.
Attach the positive and negative battery charger leads to the
terminal strip in the controller. The positive lead is either a red
wire or is marked with a (+) or (15B) designation. The nega-
tive lead is black and/or marked with a (-) or (0) designation.
The positive lead attaches to the terminal labeled "15B". Note
that there will be two wires attached to the "15B" terminal
when the full installation is completed. One for the battery
charger and one for the common connection to the transfer
switch. The negative lead attaches to the terminal labeled "0"
(Figure 3.9).
Section 3 — Standard or Service Entrance Transfer Switch Installation
Charger Mounting
Battery Charger Installation Guidelines
Figure 3.9 — Connection of Charger DC Output Wires in
Generator Control Panel
3.
Using wire nuts attach the 120VAC input wires from the bat-
tery charger to the generator backed-up 120VAC circuit from
the transfer switch (Figure 3.10).
Figure 3.10 — Connection of Charger AC Input Wires in
Generator Control Panel
4.
Dress all wires neatly (Figure 3.11).
Figure 3.11 — Completed Charger Connections on
Generator Control Panel