Figure 2.5 – 400A Switch Auxiliary Contacts
Side views shown in Utility position
3.1 FUNCTIONAL TESTS AND
ADJUSTMENTS
Following transfer switch installation and intercon-
nection, inspect the entire installation carefully.
A competent, qualified electrician should inspect
it. The installation should comply strictly with all
applicable codes, standards, and regulations. When
absolutely certain the installation is proper and cor-
rect, complete a functional test of the system.
Perform functional tests in the exact order pre-
sented in this manual, or damage to the switch
could be done.
IMPORTANT: Before proceeding with functional tests, read and
make sure you understand all instructions and information in this
section. Also read the information and instructions of labels and
decals affixed to the switch. Note any options or accessories that
might be installed and review their operation.
3.2 MANUAL OPERATION
Do NOT manually transfer under load.
Disconnect transfer switch from all power
sources by approved means, such as a main
circuit breaker(s).
A manual HANDLE is shipped with the transfer switch. Manual
operation must be checked BEFORE the transfer switch is operated
electrically. To check manual operation, proceed as follows:
1.
Ensure the generator is in the OFF mode.
2.
Turn OFF (or OPEN) both UTILITY and EMERGENCY power
supplies to the transfer switch, with whatever means provided
(such as the main line circuit breakers).
3.
Note position of transfer mechanism main contacts by
observing display windows in "A" and "B" in Figure 3.1 as
follows:
• Window "A" ON, Window "B" OFF - LOAD terminals (T1, T2)
are connected to utility terminals (N1, N2).
• Window "A" OFF, Window "B" ON - LOAD terminals (T1, T2)
are connected to emergency terminals (E1, E2).
Do not use excessive force when operating the
transfer switch manually or the manual handle
could be damaged.
3.2.1 CLOSE TO NORMAL SOURCE SIDE
Before proceeding, verify the position of the switch by observing
window "A" in Figure 3.1. If window "A" reads "ON", the contacts
are closed in the normal position, no further action is required. If it
reads "OFF", proceed with Step 1.
• Step 1: With the handle attached to the actuating shaft, move
handle in the direction of the arrow on the switch cover
until it stops — DO NOT FORCE. Release handle slowly
to allow the spring in the switch box to relax. "ON" now
appears in Window "A" and "OFF" appears in Window
"B".
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
Before proceeding, verify the position of the switch by observing
window "B" in Figure 3.1. If window "B" reads "ON", the contacts
are closed in the EMERGENCY (STANDBY) position. No further
action is required. If it reads "OFF", proceed with Step 1.
• Step 1: With the handle attached to the actuating shaft, move
the handle in the direction of the arrow on the switch
cover until it stops - DO NOT FORCE. Release handle
slowly to allow the spring in the switch box to relax.
"OFF" now appears in Window "A" and "ON" appears
in Window "B".
3.2.3 RETURN TO NORMAL SOURCE SIDE
Manually actuate switch to return Window "A" to the "ON" position.
3.3 VOLTAGE CHECKS
3.3.1 UTILITY VOLTAGE CHECKS
1.
Turn ON the UTILITY power supply to the transfer switch with
whatever means provided (such as the UTILITY maim line
circuit breaker).
P ROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT.
CONTACT WITH LIVE TERMINALS RESULTS
IN EXTREMELY HAZARDOUS AND POSSIBLY
FATAL ELECTRICAL SHOCK.
Operation
Generac ® Power Systems, Inc.
7
7