Technical specifications
Voltage measurement
Impedance measurement
Prospective short circuit
measurement
General specifications
Safety
Power supply
Mechanical specifications
Dimensions
Weight Masse
Supply
To order
Loop tester
Voltage V L-E (line - earth)
Impedance Z L-E (line - earth)
Impedance Z L-N (line - neutral)
Prospective short circuit current
Line - neutral
Prospective short circuit current
Line - earth
Impedance of the neutral wire
Impedance of the line wire +
internal impedance of transformer
Impedance of the earth wire
(including earth impedance itself)
Do a new test by connecting the tester to the circuit under test.
50 - 275VAC (50Hz only)
± 1% between 210 and 250VAC
accuracy
± 3% otherwise
:
0.03 – 2000Ω (auto-ranging)
accuracy :
20% + 10pts between 0.5 and 5Ω
10% + 10pts between 5 and 500Ω
Unspecified 0.3 to 0.5 and from 500 to 2000.
0 – 6kA to 230V
AC
IEC-61010 (EN 61010), Cat. III, 270 V
6 batteries 1.5 V (R6P) or equivalent
205 x 90 x 55 mm
~ 535 g (battery included)
EIT 800..........................................................................P06234701
Delivered in a yellow carrying case with :
3 test leads with crocodile clip
batteries
user's manual in five languages
English
(500A following field details).