Safe Use Instructions — MVS205
Specifications
POWER
Input at 0 to 75°C: 8 to 30 V dc, 245 mW average.
Input at -40 to 0°C: 8.5 to 30 V dc, 245 mW
average. Supplied by ROC/FloBoss.
ENVIRONMENTAL
Operating Temperature: —40 to 75°C.
Storage Temperature: —50 to 85°C.
Operating Humidity: 0 to 99%, non-condensing.
Radiated/Conducted Immunity: Meets
requirements of IEC 61326 Electrical Equipment
for use in Industrial Locations.
Radiated Emissions: Meets EN 55022 Class B and
ICES-003:1997 Digital Apparatus.
WEIGHT
Including head, 3.0 kg.
APPROVALS
ATEX/IECEx
Evaluated per the following European standards:
EN 60079—0 (2006).
EN 60079—1 (2007).
EN 61241—0 (2006)
EN 61241—1 (2004)
EN 60529 (2001).
Certified by KEMA as Model MVS205R.
Product Markings for Hazardous Locations:
Ex d IIB T5 (T
=75°C).
amb
Ex tD A21 IP66 T85°C.
II 2 GD.
0081.
ATEX Cert. KEMA 04ATEX2182 X
IEC Cert. IECEx KEM 07.0055X
The following tools are required for installation,
maintenance, and troubleshooting:
Personal computer (PC) running Microsoft
®
Windows
2000 (with Service Pack 2),
Windows Vista, or Windows 7.
ROCLINK™ 800 Configuration Software.
Phillips (cross-head) screwdriver.
Flat-head screwdriver.
Hex socket wrench (3/8-inch).
Hex socket wrench (7/16-inch).
Allen hex wrench (3 mm).
1. Remove the MVS205 sensor from the
shipping box.
2. Find a suitable location for the MVS205
sensor. Check all clearances when choosing
an installation site. Provide adequate
clearance for wiring and service.
3. The Coplanar™ flange on the bottom of the
MVS205 Sensor body allows mounting on a
pipestand, wall, panel, or to the flange taps of
an integral orifice assembly or manifold valve.
The MVS205 can be mounted to a panel or
pipe (see Figure 3, Figure 4, and Figure 5) with
the optional bracket kit, which includes an L-
shaped bracket and a pipe clamp. The bracket
kit attaches to the coplanar flange at the
pressure connector.
B
C
A
Cover clamp
B
Electronics head
C
Pressure connector
D
½ - 14 NPT field wiring entry
E
External ground lug location
Figure 2. MVS205 Multi-Variable Sensor
4. The process pressure inputs are piped to the
¼-18 NPT connections on the bottom of the
MVS205 or to an intervening manifold valve.
®
You also mount the MVS205 directly to flange
taps using a manifold valve or an integral
orifice assembly (not shown).
5. Use the field wiring entries to bring the wiring
into the MVS sensor electronics head. Metal
pipe plugs must remain in place on unused
wiring entries to maintain flame-proof
integrity of enclosure.
Cable Connection
The cable entry device shall be certified in
type of explosion protection flame-proof
enclosure "d", suitable for the conditions of
use and correctly installed. For ambient
temperatures over 70°C, use cables and cable
glands suitable for at least 90°C.
Part D301205X012
Page 2
A
D
E