LERBAKKEN 10, 8410 RØNDE DENMARK.
For safe installation of 6335D or 6336D the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate
Marking
Standards
Hazardous area
Zone 0, 1, 2
T5: -40 ≤ Ta ≤ 60ºC
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5 μF
Installation notes
The Instructions provided with the equipment shall be followed in detail to assure safe
operation.
Revision date:
2010-05-28
18

IECEx Installation drawing

IECEx KEM.10.0084
Ex ia IIC T5 Ga
IEC60079-11:2006, IEC60079-0: 2007, IEC60079-26: 2006
44
43
42
41
CH1
54
53
52
51
CH2
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 μH
Ci: 2.0 nF
Version Revision
V2R0
6
335V109- IN
WWW.PRELECTRONICS.COM
Non Hazardous Area
14
13
+
12
-
11
250 < R < 1100 ohm
24
23
+
22
-
21
6335D
6336D
6335QI01
R
Barrier
R
Barrier
Ex HART
Communicator
Page:
1/1