Technical Data
Power Supply (via S-BUS)
Operating voltage U
, DC
B
Residual ripple Uss
Rated power
Output circuit (X1, X2, X3, X4)
Output voltage
Output current
Total current
General data
Isolation
Power circuitry – field bus circuit
Power circuitry – output circuit
Weight
Climatic conditions
Climatic conditions
Ambient operating temperature T
Storage temperature
Relative humidity
Air pressure in operation
Mechanical strength
Vibration acc.
Electrical safety
Protection type according to EN 60529
Finger-proof
Clearance/creepage distance
EMC
Overvoltage category
Contamination level
Terminals and connection
Single-core or finely stranded
Stripping length
Finely stranded with wire-end ferrule to DIN 46228
Max. tightening torque
All manuals and user guides at all-guides.com
B
Min.
DC 19.2 V
--
Min.
18.0 V
--
--
yes
no
0,2 kg
EN 61131-2
-25°C to +55°C
-25°C to +70°C
10% to 95%, no condensation
860 hPa to 1060 hPa
EN 60068-2-xx (more data see manual)
IP 20
EN 50247
EN 61131-2
EN 61000-4-xx (more data see manual)
III
2 inside, 3 outside
screw-type terminals
1 x 0.2 - 2.5 mm² / 2 x 0.2 - 0.75 mm²
1 x 0.25 - 2.5 mm² / 2 x 0.25 - 0.5 mm²
0.5 to 0.6 Nm
Typ.
DC 24 V
--
Typ.
24 V
--
--
spring-type terminals
2 x 0.2 - 1.5 mm²
max. 8 mm
2 x 0.25 - 1.5 mm² (trapezoid crimping)
---
Max.
DC 30 V
3.0 V
1 W
Max.
30 V
100 mA
200 mA
7