Descargar Imprimir esta página

Johnson Controls MR12DR230-1C Manual De Instrucciones página 4

Publicidad

4
P
ositive temperature cold room
Defrost functions
Defrost is initiated and terminated by a timer. The
user sets the interval between successive cycles and
its duration.
During the defrost cycle, the display can show
either the last measurement before this cycle or
the setpoint. You can also delay the normal
display function after the defrost cycle has
ended.
Manual defrost is possible by pushing a key on the
controller keypad.
Fan management functions
You can choose whether the fan is to be run in
parallel with the compressor or whether it should
remain constantly ON. In this case the fan will be
ON during defrost. This will decrease defrosting
duration.
Fan and
compressor
switched in parallel
Pump down selection
A selector is available to choose between the start
stop strategy for the compressor.
Solenoid valve and
compressor
switched in parallel
Selection table:
Item code
Power supply
V ac
230
CR-PS037-1
230
CR-PS075-1
230
CR-PS110-1
230
CR-PS150-1
400
CR-PT150-1
400
CR-PT250-1
400
CR-PT400-1
400
CR-PT550-1
400
CR-PT750-1
Catalogue Section 9
All manuals and user guides at all-guides.com
Continuous
fan
Pump down
Compressor
Power
Φ Φ Φ Φ
AC-3
Amps
1
0,37 kW
5
1
0,75 kW
8
1
1,1 kW
10
1
1,5 kW
12
3
1,5 kW
3,5
3
2,5 kW
5,7
3
4,0 kW
8,5
3
5,5 kW
11,5
3
7,5 kW
15,5
Condensing fan
On the 3-phase models, two terminals are
available to field connect a condensing fan.
Digital input functions
All defrost controllers are equipped with a digital
input performing the following functions:
Shut-OFF: If the contact is open for a preset
time, all outputs are de-energised and an
alarm message is displayed.
External alarm: Display shows AL, the Alarm
output is switched ON, all other functions will
perform as normal
Door open: In this case the High alarm will
be disabled, other functions will perform as
normal.
Note:
A detailed list of available parameters and their
description can be found at the end of this
documentation.
Positive Temperature Cold Room Cabinet
Evap. Fan
Cond.
Fan
Amps
Amps
1,6
-
1,6
-
3,2
-
4,8
-
3,2
3
3,2
3
4,8
3
4,8
3
4,8
3
© 2000 Johnson Controls, Inc.
CR1
Cabinet
Shipping
weight
size
modules
Kg
12
2,2
12
2,2
12
2,2
12
2,2
18
3,2
18
3,2
18
3,2
18
3,2
18
3,2

Publicidad

loading