Toshiba SUPER-HRM MMY-MAP0802FT8 Manual De Instalación página 8

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 93
Model name
Nominal
MMY-
(V-ph-Hz)
MAP0802FT8
400-3-50
MAP1002FT8
400-3-50
MAP1202FT8
400-3-50
AP1602FT8
400-3-50
AP1802FT8
400-3-50
AP2002FT8
400-3-50
AP2402FT8
400-3-50
AP2602FT8
400-3-50
AP2802FT8
400-3-50
AP3002FT8
400-3-50
Design of control wiring
Power supply
single phase
220-240V 50Hz
(Open)
Earth
[Central remote controller]
(Option) TCB-SC642TLE
(For Line 64)
Control wiring between
outdoor unit and indoor unit
• Wire specification, quantity, size of crossover wiring and remote controller wiring
Name
Crossover wiring
(indoor-indoor / indoor-outdoor / outdoor-
indoor control wiring, central control wiring)
Remote controller wiring
Indoor unit - FS unit control wiring
(1) The crossover wiring and central control wiring use 2-core non-polarity transmission wires. Use 2-core shield wires to
prevent noise trouble. In this case, close (connect) the end of shield wires, and perform the functional grounding for
the end of the shield wires which are connected to both indoor and outdoor units.
For the shield wires which are connected between the central remote controller and the
outdoor unit, perform the functional grounding at only one end of central control wiring.
(2) Use 2-core and non-polarity wire for remote controller. (A, B terminals)
Use 2-core and non-polarity wire for wiring of group control. (A, B terminals)
Voltage
range
Unit No. 1
Min. Max.
RLA
LRA
342
457
5.2 + 5.2
342
457
6.5 + 6.5
342
457
9.5 + 9.5
342
457
5.2 + 5.2
342
457
6.5 + 6.5
342
457
6.5 + 6.5
342
457
5.2 + 5.2
342
457
6.5 + 6.5
342
457
6.5 + 6.5
342
457
6.5 + 6.5
Control wiring
between
outdoor units
FS unit
Q'ty
2 cores
2 cores
Use the transmission wire (6m) attached to FS unit. If the indoor unit is placed 5m or more
apart from the FS unit, use the connecting wire (RBC-CBK15FE (16m)) sold separately.
Compressor
Unit No. 2
Unit No. 3
RLA
LRA
RLA
LRA
5.2 + 5.2
5.2 + 5.2
6.5 + 6.5
5.2 + 5.2
5.2 + 5.2
5.2 + 5.2
5.2 + 5.2
6.5 + 6.5
5.2 + 5.2
6.5 + 6.5
6.5 + 6.5
Legend
MCA
MOCP : Maximum Overcurrent Protection (Amps)
ICF
RLA
LRA
FLA
kW
NOTE : RLA is based on the following conditions.
Connection of shield wire must be connected
(Connected to all connecting sections in each indoor unit)
FS unit
FS unit
Control wiring between indoor unit and FS unit
FS unit
Size
Up to 500m
Up to 1000m
1.25mm²
0.5 to 2.0mm²
4
Fan Motor
kW
FLA
0.6
1.0
0.6
1.1
0.6
1.1
0.6 × 2 1.0 +1.0
0.6 × 2 1.0 + 1.1
0.6 × 2 1.1 + 1.1
0.6 × 3 1.0 + 1.0 + 1.0
0.6 × 3 1.1 + 1.1 + 1.0
0.6 × 3 1.1 + 1.1 + 1.0
0.6 × 3 1.1 + 1.1 + 1.1
: Minimum Circuit Amps
: Maximum Instantaneous Current Flow Start
: Rated Load Amps
: Locked Rotor Amps
: Full Load Amps
: Fan Motor Rated Output (kW)
Indoor temperature
Outdoor temperature : 35°C DB
FS unit
<Group control>
FS unit
Wired
remote controller
1000 to 2000m
2.0mm²
Power Supply
MCA
MOCP
ICF
20.0
30
22.5
30
24.5
30
40.0
50
42.5
50
45.0
60
60.0
70
62.5
70
65.0
80
67.5
80
: 27°C DB/19°C WB
FS unit
Specification
Shield wire

Publicidad

Tabla de contenido

Solución de problemas