Set concentration
This function sets the current corresponding to any
concentration value between 0 and full-scale.
1. Select Settings > Communication > Analog interface >
Set concentr. and confirm.
2. Once the alarms at the central controller are inhibited,
confirm the message Inhibit all alarms.
3. Select the line for editing the concentration and confirm.
4. Set the concentration and confirm.
The setting for the concentration is displayed.
5. Select Next and confirm.
6. Select Set concentr. out or Concentration off and
confirm.
7. Select Next and confirm.
The function is terminated.
8. Once the alarms at the central controller are enabled
again, confirm the message Enable all alarms.
Set fault
This function sets the current to the fault current.
1. Select Settings > Communication > Analog interface >
Set fault and confirm.
2. Select Enable or Disable and confirm.
26
Set warning
This function sets the current to the warning current.
1. Select Settings > Communication > Analog interface >
Set warning and confirm.
2. Select Enable or Disable and confirm.
Set maintenance
This function sets the current to the maintenance current.
1. Select Settings > Communication > Analog interface >
Set mainten. and confirm.
2. Select Enable or Disable and confirm.
Set beam block signal
This function is only available for Polytron 87x0 (using the
sensor PIR 7x00).
5.9.3
Modbus
For further information regarding the configuration of the
modbus interface consult the Technical Modbus Handbook,
NOTICE
i
i
Using the fieldbus interface no relays are available.
The fieldbus interface is not in accordance with the
BVS 13 ATEX G 001 X.
5.9.4
Profibus address
For further information regarding the configuration of the
Profibus PA or Foundation Fieldbus H1 interface consult:
- Technical Profibus Handbook or
- Technical Fieldbus Handbook
NOTICE
i
i
Using the fieldbus interface no relays are available.
The fieldbus interface is not in accordance with the
BVS 13 ATEX G 001 X.
Dräger Polytron 8100