Siemens Sitrans LR200 Guía Rápida página 8

Ocultar thumbs Ver también para Sitrans LR200:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 59
Wiring
1
Power
WARNINGS:
DC terminals shall be supplied from an SELV
with IEC-1010-1 Annex H.
All field wiring must have insulation suitable for rated voltages.
Connecting SITRANS LR 200 (PROFIBUS PA)
Note:
For detailed wiring instructions, please see the full manual.
2 mm lid-lock set
screw.
1.
If you want to rotate the instrument on the process
connection, use the 2 mm Allen key provided to loosen
the locking ring (see illustration on page 2).
3
Use the Allen key to loosen the lid-lock set screw.
Using a screwdriver for leverage if necessary, unscrew the cover.
4.
Connect the wires to the terminal as shown: the polarity is identified on the terminal
block.
5.
Ground the instrument according to local regulations.
6.
Ground the shield according to PROFIBUS PA guidelines.
7.
Close the lid and secure the locking ring before programming and calibration. Do not
rotate the instrument after calibration, as this may cause an error.
Note:
PROFIBUS PA MUST be terminated at both extreme ends of the cable for it to work
properly. Please refer to the PROFIBUS PA User and Installation Guidelines (order number
2.092), available from www.profibus.com
1.
Safety Extra Low Voltage
2.
For general purpose applications:
- ground the shield at one point only and continue the shield from device to device.
For Intrinsically Safe applications:
- ground the shield at each device, and use an equal-potential grounding grid.
For more detail on Explosion Protection, you can download the brochure
Explosion Protection
(part number A5E00265440) from https://pia.khe.siemens.com/index.asp?Nr=4236 .
Page EN-6
SITRANS LR 200 (PROFIBUS PA) – QUICK START MANUAL
All manuals and user guides at all-guides.com
1
source in accordance
2
2
Siemens Process Automation
7ML19985QG81

Publicidad

Tabla de contenido
loading

Tabla de contenido