MASTERVISION MODULAR SWITCHBOARDS
CAUTION
1. Lethal voltages exist on your vessel. Make sure all shore power, onboard
generating sources and batteries are disconnected before beginning
installation of your electrical panel.
2. AC modules will have lethal voltages on the bus bars and terminals. The
coating on these bars is for identification only and should not be relied on
as a insulator.
Additional safety enclosures may be required in some installations.
3. Make sure all AC modules are bonded to the shipís AC ground bus. When
grouping modules together to form your panel, a single ground may be used.
Use a resistance meter to verify ground to all modules.
The basic remote panel
The basic remote panel is a useful power device for remote
control of the Mass an Ivo smart Mastervolt battery chargers.
The basic remote control does indicate the status of the charge
control by six high power leds.
The remote control is easy to install by a plug-in standard
twisted six pole RJ45 telephone plug between the analog
output of the charger and the panel. The communication of the
remote control and charger is based on analog technology.
The remote panel can be used as an interface for a custom
made panel or for a dual remote indicator.
The basic remote panel has a combined CSI-DC/alarm
(csi=charger status interface).
The potential free change-over contacts indicate if the
charger is ON or in general failure. The DC alarm set
points can be adjusted in the chargers by use of the
adjustment interface.
Specifications
Remote cable:
Connector
Max length
Type
External led drive:
Imax
Umax
General CSI alarm
Max rating
NC-on
When the charger is off or the charger is in
failure, the normally closed contact is closed
C
Common
NO-on
When the charger is on and no-failure is
indicated the normally open contact is closed
Connectors
These products fully comply to the latest CE
standards in force from January 1st 1996
and are produced to ISO 9001 standards.
ISO 9001
102
RJ45, 6 pole, male
6 meter, max
reversed wire
5 mA
2,5V
1 Amp, 30 VDC
0,75 mm2
SPECIFICATIONS
description:
type:
dimensions panel (wxh):
panel depth:
Charger Control
Charger Control
Inverter Control
Charger Control
Charger Output
failure
absorption
failure
failure
absorption
on - bulk charge
absorption
current control
alarm contact
Combined CSI failure and DC high/low alarm
Bat TC failure
Battery temperature sensor out of range <20°C & >60°C
Voltage sense failure
Voltage sense out of range >3 VDC
Sys. temp. failure
Charger is out of temperature range ìoverloadî (>75--85 C)
Short break indicator
Charger in reduced current mode (short break mode) Uout <4..5VDC
DC alarm
Battery range out of range (with standard setting of charger)
panel code
part number
07-04-04100
remote basic charger control
for Mass & IVO smart chargers
60 x 65 mm
40 mm
float
on
on
on
float
float
bulk
failure
bulk
common
C
normal open
normal closed
NC
DC+CSI
1 2 3 4 5 6
6 pole telephone jack
RJ 45
charger
1 2 3 4 5 6
12V
24V
DC low on
10.0
20.0
DC low off
11.0
22.0
DC high on
16.0
32.0
DC high off
15.0
30.0
Delay time
30
C-4-RB
NO
VDC
VDC
VDC
VDC
30
SEC
Appendix B