Installation equipotential bonding for sealing end range / Verlegung Potentialausgleichsleiter Endverschluss
EB conductor parallel HVI
Situation
PA-Leiter parallel HVI
1, 2, 3
no / nein
1
yes / ja
1
yes / ja
2
yes / ja
2
yes / ja
Installation example of an EB conductor routed in
parallel with the HVI Conductor:
The calculated separation distance "s (solid material)"
between the HVI Conductor and the EB conductor is 50 cm.
The EB conductor is installed at a distance of 20 cm from the
HVI Conductor. Consequently, a distance of 30 cm must be
maintained between the EB conductor and conductive or
earthed parts (secondary conductor loop; no metal facade).
2
s (k
= 0,5)
m
s
relevant
X1
s
relevant (km=0,5)
no / nein
yes / ja
yes / ja
yes / ja
yes / ja
3
X1
X
X
1 relevant
2 relevant
no / nein
no / nein
yes / ja
X
< s - X
2
1
yes / ja
X
≥ s - X
2
1
X
< s
no / nein
1
X
≥ s
no / nein
1
Beispiel Verlegung parallel geführter PA-Leiter:
Der errechnete Trennungsabstand "s (fester Stoff)" zwischen
HVI Leitung und PA-Leiter beträgt 50 cm. Der PA-Leiter ist im
Abstand von 20 cm zur HVI Leitung verlegt. Somit ist
zwischen PA-Leiter und elektrisch leitfähigen bzw. geerdeten
Teilen (sekundäre Leiterschleife; keine Metallfassade) ein
Abstand von 30 cm einzuhalten.
SPD
Non-critical inductive coupling /
Induktionswirkung unkritisch
(Typ 2 recommended/empfohlen)
Typ 2
Non-critical inductive coupling /
Induktionswirkung unkritisch
(Typ 2 recommended/empfohlen)
Typ 2
Non-critical inductive coupling /
Induktionswirkung unkritisch
(Typ 2 recommended/empfohlen)
27