Press "Menu"
2
Select group 02 ORIENTED START-UP
- Change the content of P0317 for "[001] Yes".
3
- Press "Save".
and the "config" status is indicated on the upper part of the HMI
- Select the desired language.
4
- Press "Save".
IMPORTANT: the PM with encoder control mode must be
selected only when the motor is equipped with encoder (speed
sensor).
5
- Select the control mode: [002] V/f Adjustable, [006] PM with
encoder or [007] Sensorless PM.
- Press "Save".
- Set P0296 according to the line rated voltage.
6
- Press "Save" .
Set P0298 according to the application:
ND: normal duty overloads for long periods.
HD: heavy overloads for short periods.
7
For further information, refer to the inverter overload curves in
Chapter 8 Technical Specifications of the User's Manual.
For type of control [002] V/f adjustable, it is necessary to select
the motor type in P0396. Set P0396 to [001] PMSM (VVW PM).
The next parameters must be set according to the motor nameplate.
- Change the content of P0398 according to the motor service
8
factor.
- Press "Save".
- Change the content of P0400 according to the motor rated
9
voltage.
- Press "Save".
- Change the content of P0401 according to the motor rated
10
current.
- Press "Save".
Procedure for oriented start-up
At this moment, the oriented start-up routine starts
PM Sensorless
PM Sensorless
400 V
400 V
Normal Duty
(
)
{
}
x
1.00
1.00
400 V
400 V
26.1 A
W22 Magnet Drive System
and W50 Magnet | 5
®