2.2
Cableado
Este capítulo describe las diferentes alternativas de conexionado básico para la aplicación de bombeo solar.
2.2.1 Señales de entrada y salida
Tabla 2.2-1 Describe las señales de entrada del variador.
INPUT
Water tank level analog signal. The signal from the water level sensor of the tank can
be connected to this input. The inverter will stop when the tank level becomes higher
than the level programmed in parameter U128. In order to use this signal, connect the
[12]
sensor to this input and set the desired tank level above which the pump has to stop. If
this signal is not used, set a high level in parameter U128 to avoid that the inverter
stops.
[FWD]
Run command in the FWD direction
[REV]
Run command in the REV direction
Water tank high level digital signal. This signal is ON when the level of the tank is high.
[X1]
The inverter will stop when this signal is ON. In order to use this signal, simply connect
it to the inverter; it is not required to enable it by function code.
Tabla 2.2-2 Describe las señales de salida del variador. Si es necesario, las señales de salida se
pueden programar. Configurar los parámetros E20, E21 y E27.
OUTPUT
Tank full output signal. This signal indicates that the water tank is full. In this situation
[Y1]
the inverter will not be allowed to RUN, therefore this signal is useful to
indicate/diagnose the cause of the stop.
Low power output signal. This signal indicates that the output power is low. In case
that this signal is ON and the solar irradiance is high, it is useful to detect/diagnose that
[Y2]
there is a problem in the PV solar panel (for example dust, or the panel has been
covered).
This relay output is used to indicate that the inverter has tripped by alarm. The alarm
[30A/B/C]
code is displayed in the inverter keypad.

2.2.2 Variador alimentado desde paneles solares

Hay dos alternativas a la hora de realizar el conexionado de las placas solares al variador:
(1) Conectado directamente en los terminales del bus de continua P(+) y N(-). En este caso el circuito de
precarga del variador no se utiliza. Por lo tanto, cuando las placas solares se conectan al variador, es
posible que circule una corriente muy elevada, debido a que los condensadores están descargados.
Para evitar esta situación hay dos alternativas.
Insertar circuito de precarga entre el positivo de las placas solares (+) y P(+).
o
Usar la segunda alternativa de conexión descrita en la siguiente página (figura 2.2-2).
o
Tabla 2.2-1 Señales de entrada del variador.
DESCRIPTION
Tabla 2.2-2 Señales de salida del variador.
DESCRIPTION
2-2
SYMBOL
TANK LEVEL
FWD
REV
TANK HL
SYMBOL
TANK FULL
LOW POWER
ALM