Repairing Refrigerant Leaks; Preparation For Periods Of Non-Use - HTW IX43 R32 Manual De Usuario

Ocultar thumbs Ver también para IX43 R32:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Hold the tabs of the frame,and remove the
4 claws. (The special function lter can be
washed with water once every 6 months. It
isrecommended that you replace it once
every 3 years.)
Special function lter
Fig. 4.3
4. Clean the air lter by vacuuming the surface
or washing it in warm water with mild
detergent.
A. If using a vacuum cleaner, the inlet side
should face the vacuum.
Fig. 4.4
B. If using water, the inlet side should face
down and away from the water stream.
Fig. 4.5
5. Rinse the lter with clean water and allow
it to air-dry. DO NOT let the lter dry in
direct sunlight.
6. Reinstall the lter.

Repairing Refrigerant Leaks

WARNING
If the refrigerant leaks, turn o the air
conditioner and any combustible heating
devices, ventilate the room and call your
dealer immediately. Refrigerant is both toxic
and flammable. DO NOT use the air
conditioner until the leak is repaired.
When the air conditioner is installed in a
small room, measures must be taken to
prevent the refrigerant concentration from
exceeding the safety limit in the event of
refrigerant leakage. Concentrated
refrigerant causes a severe health and safety
threat.
Refrigerant Leak Detection System (some
models)
In the event of a refrigerant leak, the LCD
screen will display "EC" and the LED
indicator light will flash.

Preparation For Periods Of Non-Use

Maintenance after Extended Non-Use
1. Remove any obstacles blocking the vents of
both the indoor and outdoor units.
2. Clean the air lter and the front grille of the
indoor unit. Reinstall the clean, dry air lter in
its original position.
3. Turn on the main power switch at least 12
hours prior to operating the unit.
Storing the Unit While Not In Use
1. Run the appliance on FAN mode for 12 hours
in a warm room to dry it and prevent mold.
2. Turn o the appliance and unplug it.
3. Clean the air lter according to the
instructions in the previous section. Reinstall
the clean, dry lter before storing.
4. Remove the batteries from the remote control.