60313.16.03
Page 2: Counters
•
Hour Meters indicate the hours that: the controller has been powered up,
and the compressor has been running.
•
Starts indicate the number of times a start is attempted on the
compressor.
Date & Time is adjustable and configurable in the GENERAL SETTINGS
•
folder.
All information on this page is read only .
Pages 3-5: Analog Inputs & Compressor Information
Figure 60: Analog Inputs & Compressor Information
All information on these pages is read only .
The following analog inputs are displayed in this section:
•
Package Discharge Pressure
•
Sump Pressure
•
Airend Discharge Temperature
•
Injected Coolant Temperature
•
Aftercooler Discharge Temperature
•
Separator Pressure Drop
•
Coolant Filter Pressure Drop
•
Inlet Vacuum
•
Remote Pressure (optional)
•
Aftercooler Discharge Pressure (integrated dryer compressors only)
EN-
All manuals and user guides at all-guides.com
Figure 59: Counters
NOTICE
Icon
Meaning
Pressure
Temperature
NOTICE
Additionally, the following compressor status readings are included in this
section:
•
Motor Speed
•
Package kW
•
Average Package kW/hour
•
Average % Capacity
•
Average Capacity
•
Energy Cost
•
Energy Savings
•
Lifetime Energy Savings
Operator settings folder
Pages 1-2: Operator Settings
Figure 61: Operator Settings
The parameters below are adjustable at any time:
Table 22: Operator Settings
Operator
Default
Settings
Target Pressure
100
Automatic Stop
110
Target+1
Pressure
Immediate Stop
120
Pressure
% Savings
Modulation
Compared To
Energy Rate
0.000
Reset Averaging
--/--/--
EN
Min .
Max .
Step
Unit
65
145
1
psi
Target+10
1
psi
Auto
Auto+10
1
psi
---
---
---
---
0.000
9999.999
---
---
-
-
-
date
80446339 Rev C