16TH EDITION REGULATIONS AND CALOREX UNITS
CAN BE WITHIN 1,25M BUT
MUST THEN BE 2,5M ABOVE
POOL SURFACE
1) N.B. THE RCD IS AN EARTH LEAKAGE TRIP & ALTHOUGH NOT ALWAYS REQUIRED
IT IS RECOMMENDED THAT IT IS USED ON ALL INSTALLATIONS. (A 30mA RCD SHOULD BE USED).
2)THE ISOLATOR FOR THE DEHUMIDIFIER MUST COMPLY TO THE APPROPRIATE IPX REGULATION
ALTHOUGH THE UNIT IS 2,5M
ABOVE THE HEIGHT OF THE
POOL IT IS NOT ACCESSIBLE
FOR SERVICE & SO BREAKS
THE NEW REGULATIONS
1,25 - 2,0M MUST BE FITTED WITH AN RCD
AND BE AT LEAST 300mm FROM FLOOR
Page 3
MUST BE FITTED WITH RCD
2,0-3,5M
ANY HEIGHT ACCEPTABLE
IF THE UNIT IS WITHIN 1,25M
OF THE POOL HORIZONTALLY
THEN IT MUST BE 2,5M ABOVE
THE POOL SURFACE.