4.1 OPTIONAL HUMIDISTAT/AIRSTAT

12V REMOTE HUMIDISTAT CONNECTIONS
HUMIDISTAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX
PART SD385250.
SIEBE PART No.119 1701
91100)
250M MAX
1mm SQ CABLE
WITH REMOTE HUMIDISTAT FITTED ENSURE HUMIDISTAT
IN MACHINE IS SET FULLY CLOCKWISE (IE MAXIMUM DEHUMIDIFICATION)
REMOVE PINK WIRE LINK
AIR STAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX
PART SD385251.
INVENSIS TYPE RTR-E6705,
PART No.111 170951 100).
250M MAX
1mm SQ CABLE
12V REMOTE AIR THERMOSTAT CONNECTIONS
FOR M/C WITH RESISTANCE HEATERS OR LPHW
All manuals and user guides at all-guides.com
12V REMOTE AIR THERMOSTAT CONNECTIONS
8
7
6
5
4
3
2
1
8
7
6
5
4
AIR STAT
3
L (L1)
2
N (L2)
1
E (GND)
Page 8
BOILER DEMAND
REMOVE
SIGNAL VOLT FREE
LINK
COMMON
HUMIDISTAT
AIR STAT
L (L1)
N (L2)
E (GND)
BOILER DEMAND
SIGNAL VOLT FREE
COMMON
HUMIDISTAT