P19.09
Average frequency threshold [NLO]
P19.10
Average frequency threshold [FLO]
P19.11
Average frequency threshold [FHI]
P19.12
Average frequency threshold [NHI]
P19.13
DIP threshold
P19.14
SWELL threshold
P19.15
DIP/SWELL hysteresis
P19.16
Waveform capture on DIP/SWELL
P19.17
Interruption threshold
P19.18
Interruption hysteresis
P19.19
Waveform capture on interruption
P19.01 Global enabling of the energy quality control function.
P19.02, P19.05 Extreme thresholds applied to the integrated voltage, for the generation of NHI and NLO events, with an
increase in the relative counters.
P19.03, P19.04 Voltage thresholds for the generation of VLO and VHI events and weekly, monthly and annual energy
quality percentages.
P19.06 Harmonic distortion quality control mode.
OFF: disabled.
THD: control based on THD, with threshold adjustable via P19.07.
HAR: control based on the percentage of the single voltage harmonics, from the 2nd to the 25th order, with thresholds
defined as per the EN50160 standard.
P19.07 Total harmonic distortion (THD) threshold for the generation of THD events and weekly, monthly and annual
energy quality percentage count.
P19.08 Voltage asymmetry threshold for generating asymmetry events and counting the weekly, monthly and annual
energy quality percentages.
P19.09, P19.12 Extreme thresholds applied to the integrated frequency, for the generation of NHI and NLO events, with
an increase in the relative counters.
P19.10, P19.11 Frequency thresholds for the generation of FLO and FHI events and weekly, monthly and annual energy
quality percentages.
P19.13 Threshold for generation of DIP event (fast voltage drops).
P19.14 Threshold for generating the SWELL event (fast voltage rises).
P19.15 Hysteresis for the previous two thresholds.
P19.16 Enables the capture of the waveform on DIP or SWELL event.
P19.17 Threshold for generating interruption event.
P19.18 Hysteresis for the previous threshold.
P19.19 Enables the capture of the waveform on an interruption event.
M20 EASY
P20.n.01 Load type
P20.n.02 CT primary (I1-I2-I3)
P20.n.03 CT secondary (I1-I2-I3)
P20.n.04 Voltage source
P20.n.05 Modbus addres
P20.n.06 Accumulator number
P20.n.01 Type of load associated with the measuring point.
OFF: input disabled
3ph: the three current inputs measure a three phase load
3x1ph: the three current inputs measure three single phase loads, one for each phase. For the choice of the reference
voltage, see P20.n.04.
1ph: only one of the three current inputs (I1) is connected and measures a single phase load.
P20.n.02 Rated current of the CT primary.
P20.n.03 CT secondary current.
P20.n.04 Voltage source to which the loads are connected, in the case of P20.n.01 = 3x1ph or 1ph.
L1 L2 L3: valid for the 3x1ph case, I1 is associated with L1, I2 with L2 and I3 with L3
L1 L1 L1: I1, I2, I3 use L1 as the reference voltage
L2 L2 L2: I1, I2, I3 use L2 as the reference voltage
L3 L3 L3: I1, I2, I3 use L3 as the reference voltage.
P20.n.05 Modbus node associated with the measurement point for reading from remote software. The data network
must be connected to the main multimeter to which the EASY Branch system is connected: through this, the remote
software queries the various measuring points as if they were independent multimeters, each with its own modbus node.
P20.n.06 Association of the measuring point to a virtual sum point: total and partial active energy and active power are
added. The values are available on the EASY Branch page, they can be used in the limit thresholds and are readable via
modbus.
PARAMETER SETUP WITH NFC
Thanks to NFC technology, it is possible to configure and modify parameters (even when the power analyzer is not powered)
through the LOVATO NFC App which can be downloaded for free from the Google Play Store and App Store for Android and iOS
smart devices. The same menus and parameters available on the display are presented and it is possible to save the
configuration file compatible with the built-in web server and with the Xpress configuration software.
INFRARED OPTICAL PORT
The optical port on the back of the power analyzer is compatible with CX01 and CX02 communication devices.
With CX01 it is possible to connect with the Xpress software (freely downloadable at www.lovatoelectric.com web site) for:
the configuration of the parameters;
electrical network diagnostics;
firmware update of the power analyzer.
With CX02 it is possible to connect with the LOVATO Electric SAM1 app that can be downloaded for free from the Google Play
Store and App Store for Android and iOS smart devices for:
the configuration of the parameters;
electrical network diagnostics;
the clone of the data memory, for example to transfer the values of the energy meters from one DMG to another.
The optical port is located under the cover of the second expansion slot.
%
94.0
OFF / 80-100
%
99.0
OFF / 80-100
%
101.0
OFF / 100-120
%
104.0
OFF / 100-120
%Un
90.0
OFF / 5-100
%Un
110.0
OFF / 100-150
%
2.0
0-10.0
OFF
OFF-ON
%Un
5.0
OFF / 0.1-10.0
%Un
1.0
0-10.0
OFF
OFF-ON
UdM
Default
Range
3ph
OFF
3ph
3x1ph
1ph
A
5
1-10000
A
5
1/5
L1-L2-L3
L1-L2-L3
L1-L1-L1
L2-L2-L2
L3-L3-L3
n+1
2-254
OFF
OFF / 1-8
P19.09
Soglia frequenza media [NLO]
P19.10
Soglia frequenza media [FLO]
P19.11
Soglia frequenza media [FHI]
P19.12
Soglia frequenza media [NHI]
P19.13
Soglia DIP
P19.14
Soglia SWELL
P19.15
Isteresi DIP/SWELL
P19.16
P19.17
Soglia interruzione
P19.18
Isteresi interruzione
P19.19
interruzione
P19.01
P19.02, P19.05 Soglie estreme applicate alla tensione integrata, per la generazione degli eventi NHI e NLO, con
incremento dei relativi contatori.
P19.03, P19.04 Soglie di tensione per
settimanale, mensile e annuale.
P19.06 Modo controllo qualità distorsione armonica.
OFF: disabilitato.
THD: controllo basato su THD, con soglia regolabile tramite P19.07.
HAR: controllo basato sulla percentuale delle singole armoniche di tensione, dal 2.o al 25.mo ordine, con soglie definite
come da norma EN50160.
P19.07 Soglia distorsione armonica totale (THD) per la generazione degli eventi THD e conteggio percentuali qualità
, mensile e annuale.
P19.08 Soglia asimmetria di tensione per la generazione degli eventi di asimmetria e conteggio percentuali qualità
, mensile e annuale.
P19.09, P19.12 Soglie estreme applicate alla frequenza integrata, per la generazione degli eventi NHI e NLO, con
incremento dei relativi contatori.
P19.10, P19.11 Soglie di frequenza per la generazione degli eventi FLO e FHI e conteggio percentuali qualità
nergia settimanale, mensile e annuale.
P19.13 Soglia per generazione evento DIP
(abbassamenti veloci di tensione).
P19.14 Soglia per generazione evento SWELL
P19.15 Isteresi per le precedenti due soglie.
P19.16
P19.17 - Soglia per generazione evento interruzione.
P19.18 Isteresi per la precedente soglia.
P19.19
M20
P20.n.01 Tipo di carico
P20.n.02 Primario TA (1-2-3)
P20.n.03 Secondario TA (1-2-3)
P20.n.04 Sorgente di tensione
P20.n.05 Indirizzo modbus
P20.n.06 Numero accumulatore
P20.n.01 Tipo di carico associato al punto di misura.
OFF: ingresso disabilitato
3ph: i tre ingressi di corrente misurano un carico trifase
3x1ph: i tre ingressi di corrente misurano tre carichi monofase, uno per ciascuna fase. Per la scelta della tensione di
riferimento, vedere P20.n.04.
1ph: solo uno dei tre ingressi di corrente (I1) è collegato e misura un carico monofase.
P20.n.02 Corrente nominale del primario dei TA.
P20.n.03 Corrente del secondario dei TA.
P20.n.04 Sorgente di tensione a cui sono collegati i carichi, nel caso di P20.n.01 = 3x1ph oppure 1ph.
L1-L2-L3: valido per il caso 3x1ph, I1 è associato a L1, I2 a L2 e I3 a L3.
L1-L1-L1: I1, I2, I3 utilizzano L1 come tensione di riferimento.
L2-L2-L2: I1, I2, I3 utilizzano L2 come tensione di riferimento.
L3-L3-L3: I1, I2, I3 utilizzano L3 come tensione di riferimento.
P20.n.05 Nodo modbus associato al punto di misura per lettura da software remoto. La rete dati deve essere collegata
al multimetro principale a cui è connesso il sistema EASY Branch: tramite questa, il software remoto interroga i vari punti
di misura come se fossero multimetri indipendenti, ciascuno con il suo nodo modbus.
P20.n.06 Associazione del punto di misura ad un punto virtuale somma: vengono sommati energia attiva totale e
parziale e potenza attiva. I valori sono disponibili nella pagina EASY Branch, possono essere utilizzati nelle soglie limite e
sono leggibili via modbus.
IMPOSTAZIONE DEI PARAMETRI TRAMITE NFC
Grazie alla tecnologia NFC è possibile effettuare (anche ad analizzatore di rete non alimentato) la configurazione e la modifica
dei parametri attraverso la App LOVATO NFC scaricabile gratuitamente da Google Play Store e App Store per smart devices
Android e iOS. Vengono presentati gli stessi menu e parametri disponibili tramite display ed è possibile salvare il file di
configurazione compatibile con il web server integrato e con il software di configurazione Xpress.
PORTA OTTICA A INFRAROSSI
La porta ottica sul retro
è compatibile con i dispositivi di comunicazione CX01 e CX02.
Con CX01 è possibile il collegamento con il software Xpress (scaricabile gratuitamente dal sito www.lovatoelectric.com) per:
la configurazione dei parametri;
la diagnostica della rete elettrica;
l'aggiornamento firmware dell'analizzatore di rete.
Con CX02 è possibile il collegamento con la app LOVATO Electric SAM1 scaricabile gratuitamente da Google Play Store e App
Store per smart devices Android e iOS per:
la configurazione dei parametri;
la diagnostica della rete elettrica;
il clone della memoria dati, ad esempio per trasferire i valori dei contatori di energia da un DMG ad un altro.
La porta ottica si trova sotto il coperchio del secondo slot di espansione.
%
94.0
OFF / 80-100
%
99.0
OFF / 80-100
%
101.0
OFF / 100-120
%
104.0
OFF / 100-120
%Un
90.0
OFF / 5-100
%Un
110.0
OFF / 100-150
%
2.0
OFF
%Un
5.0
OFF / 0.1-10.0
%Un
1.0
OFF
(innalzamenti veloci di tensione).
interruzione.
UdM
Default
3ph
A
5
A
5
L1-L2-L3
n+1
OFF
0-10.0
OFF-ON
0-10.0
OFF-ON
Range
OFF
3ph
3x1ph
1ph
1-10000
1/5
L1-L2-L3
L1-L1-L1
L2-L2-L2
L3-L3-L3
2-254
OFF / 1-8
18