Weight of the system: Allows configuring the relevance of the system toward the
Ventilation Control Board (AZIACCV) and determining the weight of the system:
Ventilation function
desired type of ventilation in the system. Possible values are: Outside Air, Recirculate
(indoor air) or Combined.
Clim-Vent
(Only available for Innobus Air)
Climate or Ventilate (can not operate simultaneously) and Climate and Ventilate (both
functions operates simultaneously).
Global ventilation contact
ventilation in all zones. To activate this function, set the input logic between the following
values: Normally opened or Normally closed. The OFF value disables this function.
Freecooling for occupied mode
deactivating freecooling in occupied mode. If activating this parameter, the following
value will be enabled:
-
Freecooling delta: Allows setting the temperature differential to activate
frecooling in occupied mode. This option is configurable between 2ºC and 6ºC,
in steps of 1ºC. The default value is 2ºC.
Freecooling in occupied mode will be operational if: T.
the operation mode is Cooling mode or there is a cooling demand from any zone.
Frecooling for unoccupied mode
deactivating the freecooling in unoccupied mode. If activating this parameter, the
following values will be enabled:
-
Outside temperature: This parameter allows setting the desired outdoor
temperature. If T.
unoccupied mode.
-
Freecooling set point: This parameter allows setting the desired indoor
temperature. If T.
unoccupied mode.
Freecooling in unoccupied mode will be operational if, in addition to the above, the
following conditions are met:
-
Current operation mode is Stop.
-
Operation mode prior to Stop is Cooling mode.
Minimum Voltage 0-10 V: Allows configuring the minimum output voltage of the
gateway for speed control. The default value is 0.5 V. Configurable between 0 and 10 V,
in steps of 0.1V.
Weight under demand
Total ventilation weight
0 %
1 %... 33 %
34 %... 66 %
67 %... 100 %
(Only available for Innobus Air)
: Allows configuring the system operating levels as
(Only available for Innobus Air)
(Only available for Innobus Air)
(Only available for Innobus Air)
< T.
outdoor
indoor configured
< T.
indoor
outdoor configured
Speed
Stop
Speed 1
Speed 2
Speed 3
: This parameter allows selecting the
: Activates/deactivates the local
: Allows activating or
< (T.
outdoor
indoor
: Allows activating or
the freecooling will be operational in
the freecooling will be operational in
- Delta ± Hyst) and