Presence contact: Allows controlling the status of a zone based on a presence detector.
If activating this entrance, the zone air conditioning will activate the Sleep mode with
value 90. To activate this function, set the input logic between the following values:
Normally opened or Normally closed. The OFF value disables this function.
Local ventilation contact
ventilation in the zone. To activate this function, set the input logic between the following
values: Normally opened or Normally closed. The OFF value disables this function.
Heating mode: This function allows configuring the zone heating source. The options that
have to be configured are Air
heating mode from the selected zone.
Cooling mode: This menu allows configuring the cold source for the zone. This menu
takes by default the parameters configured in initial configuration. The options that have
to be configured are Air
cooling mode from the selected zone.
Dew point probe: It allows activating the zone protection from humidity for cooling floor.
In case of activation, the system uses the air source if available. To activate this function,
set the input logic between the following values: Normally Opened or Normally Closed.
The parameter OFF disables this function.
Basic mode: This option allows disabling the thermostat advanced settings leaving a
basic control to ensure ease of use. Select ON to activate the basic mode. Otherwise,
select OFF.
Ventilation: Activates/deactivates the ventilation mode in the
Room temperature: Read-only parameter that shows the room temperature of the zone.
Errors: Read-only parameter that indicates whether there are active errors in the selected
zone. In case it indicates YES, press on the parameter to display the bar and check the
active errors.
Firmware local module: Read-only parameter that indicates the local module software of
the associate zone.
Thermostat firmware: Read-only parameter that indicates the thermostat software of the
associate zone.
Q-Adapt weight: In ACUAZONE / IBPro32 / Innobus Air systems configured with manual
Q-Adapt, this option allows modifying the total weight of the zone with values between 1
and 99.
Ventilation opening
minimum air opening. This opening will be applicable only in zones with ventilation
demand. There are 3 possible steps:
Step 1: Damper opening at 25 %.
-
-
Step 2: Damper opening at 50 %.
Step 3: Damper opening at 75 %.
-
Manufacturer ID: Allows selecting the manufacturer of the Split.
(Only available for Innobus Air)
, Radiant
, Radiant
(Only available for Innobus Air)
: Activates/deactivates the local
, Combined
, Combined
and OFF that removes the
zone.
: This parameter allows configuring the
and OFF that removes the
43