Connection (continued)
Plug Your Equipment into the PDU's Outlets
5
Your UPS is designed to support electronic equipment only. You will overload your UPS if the
total VA rating for all the equipment you connect exceeds the UPS's output capacity. Do not
connect household appliances or laser printers to the UPS's outlets. To find your equipment's VA
ratings, look on their nameplates. If the equipment is listed in amps, multiply the number of amps
by the input voltage (240V or 208V) to determine VA. (Example: 1 amp × 120 = 120 VA).
Turn UPS OFF (Optional)
6
1. Press the control panel's "OFF" button
LCD screen
will display "BYPASS MODE". The inverter is now turned off, but the UPS
H
system is not fully deactivated and the load is still energized.
2. Turn off the Output Circuit Breakers
longer be energized and the LCD screen
3. Turn off the breaker for the UPS system's utility power source. The UPS system is now turned
off and the LCD screen
H
UPS Cold Start (Optional)
7
During a blackout or other input power failure, the UPS system can be "cold started" from
battery. (The battery must be at least partially charged.) Note: The UPS system's output
settings cannot be configured while operating from battery. It will use the previously
configured output settings.
1. Make sure the PDU modules manual bypass switch
2. Turn on the Output Circuit Breakers on PDU module
3. Press the control panel's "ON" button
The UPS system's inverter will begin to operate. Note: Some electronic equipment draws
more current at startup. When starting from battery, consider reducing the initial load.
4. The UPS system will perform a brief self-test and show the results on the control panel
LEDs and LCD screen
. See "Startup Self-Test" in the "Operation" section for the display
H
sequence.
5. After the self-test is complete, the LCD screen
an alarm should sound.
6. The UPS system will now provide power to connected equipment until the battery is
discharged.
Optional Connection
The following connections are optional. Your UPS system will function properly without these connections.
USB and RS-232 Serial Communication Connection
1
Use the included USB cable
1a
port of your computer to the communication port of your UPS. Install on your computer the
Tripp Lite PowerAlert Software appropriate to your computer's operating system. Consult your
PowerAlert manual for more information.
USB Communication Port Note: The USB port may be used to connect your UPS to a
workstation or server. It is used with TrippLite software and the included USB cable to monitor
and manage the UPS remotely over a network and to automatically save open files and shut down
equipment during a blackout. See "Optional Connection" for details. For USB communications,
both DIP switches must be in the ON position. This will disable the RS-232 port.
201102160 93-2897.indb 8
until you hear a beep, then release the button. The
K
located on the detachable PDU. The load will no
M
H
will be dark.
will be dark.
is set to the "NORMAL" position.
L
.
M
until the UPS system beeps, then release the button.
I
should display "ON BATTERY MODE" and
H
or RS-232 DB9 serial cable
1b
to connect the communication
8
5
1a
1b