Operation (continued)

Output Settings

Note: Any Output Setting changes require a UPS power cycle.
Output Voltage: used to set the UPS' output voltage rating. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT
SETTING screen. Press ON to reach an OUTPUT VOLTAGE screen and ON again. You can now scroll DOWNi or UPh between 5 voltage
values: 200/208/220/230/240V. Press ON to save your desired voltage.
DEFAULT: 208V
Frequency Converter: used to set the Frequency Converter Mode. From the SETUP MENU screen, scroll DOWNi until you reach the OUTPUT
SETTING screen. Press ENTER for the OUTPUT VOLTAGE screen and DOWNi to access the FREQ CONVERTER screen. Here, press ON.
Now you can scroll DOWNi or UPh between DISABLE, 50 and 60 Hz. Press ON to save your selection. When on DISABLE, the UPS will
automatically detect input frequency and select 50 or 60 Hz accordingly. The DEFAULT selection is DISABLE.