When it results that the ZONA MIX
board is connected to the boiler
The intervention of the safety thermo-
stat switches the mixed zone plant
pump, the mix zone valve closes and on
the display the anomaly ALL 22. During
this anomaly the boiler continues to func-
tion normally.
Fig. 23/r
– DELIVERY PROBE BREAKDOWN ANO-
MALY SECOND MIXED ZONE "ALL 23"
(fig. 23/s)
When it results that the ZONA MIX
board is connected to the boiler and the
delivery probe is open or short circuited
on the display the anomaly ALL 23
appears. During this anomaly the boiler
continues to function normally.
Fig. 23/s
– SOLAR S1 COLLECTOR PROBE BREAK-
DOWN ANOMALY "ALL 24" (fig. 23/t)
When it results that the INSOL solar
board is connected to the boiler and the
S1 solar collector probe is open or short
circuited on the display the anomaly ALL
24 appears. During this anomaly, the boi-
ler continues to function normally.
Fig. 23/t
– SOLARE S2 BOILER PROBE BREAK-
DOWN ANOMALY "ALL 25" (fig. 23/u)
When it results that the INSOL solar
board is connected to the boiler and the
S2 solar boiler probe is open or short
circuited on the display the anomaly ALL
25 appears. During this anomaly the boi-
ler continues to function normally.
Fig. 23/u
– S3 SOLAR PROBE BREAKDOWN ANO-
MALY "ALL 26" (fig. 23/v)
When it results that the INSOL solar
board is connected to the boiler and the
S3 solar probe is open or short circuited
on the display the anomaly ALL 26
appears. During this anomaly the boiler
continues to function normally.
Fig. 23/v
– SOLAR APPLICATION COHERENCE
ANOMALY "ALL 27" (fig. 23/w)
When it results that the INSOL solar
board is connected to the boiler and the
hydraulic configuration to the boiler is
incorrect (PAR 2) on the display the ano-
maly ALL 27 appears. During this ano-
maly, the boiler continues to function
normally and only the solar collector anti-
freeze function is active on the solar
board.
Fig. 23/w
– COMPATIBILITY INPUT (S3) ANOMALY
ONLY FOR SYSTEM 7 "ALL 28" (fig.
23/y)
When a probe is connected instead of a
clean contact on entry S3 the board on
display shows the anomaly ALL 28.
During this anomaly the boiler continues
to function normally but for the board is
active in the solar anomaly, the function
is only available antifreeze collector.
Fig. 23/y
– NUMBER OF CONNECTED BOARDS
ANOMALY "ALL 29" (fig. 23/z)
When the number of connected boards
does not correspond to the number of
boards set in the card (PAR 40) or there
is a default of communication with it, on
the display the anomaly ALL 29 appears.
During this anomaly, the boiler continues
to function normally.
ATTENTION: If the display visualizes "ALL
01" the anomaly can be caused by an
electric problem (main PCB or wiring).
ES
PT
ENG
Fig. 23/z